Tele 2390500 G2PM400VSY10 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 2390500 Hoja De Datos
Los códigos de productos
2390500
Subject to alterations and errors
Release 08/05
Monitoring relays - GAMMA series
Voltage monitoring in 3-phase mains
Multifunction
Monitoring of phase sequence and phase failure
Monitoring of asymmetry selectable
Connection of neutral wire optional
Detection of loss of neutral wire
Supply voltage selectable via power modules
1 change-over contact
Width 22.5mm
Industrial design
Technical data
1. Functions
Voltage monitoring in 3-phase mains with adjustable thresholds,
adjustable tripping delay, monitoring of phase sequence and phase
failure, monitoring of asymmetry with adjustable threshold and the
following functions (selectable by means of rotary switch)
UNDER Undervoltage
adjustable tripping delay, monitoring of phase sequence and phase
failure, monitoring of asymmetry with adjustable threshold and the
following functions (selectable by means of rotary switch)
UNDER Undervoltage
monitoring
UNDER+SEQ Undervoltage monitoring and
monitoring of phase sequence
WIN
Monitoring of window between Min and Max
WIN+SEQ
Monitoring the window between Min and Max
and monitoring of phase sequence
2. Time ranges
Adjustment
range
Start-up suppression time:
-
Tripping delay:
0.1s
10s
3. Indicators
Red LED ON/OFF:
indication of failure
of the corresponding threshold
Red LED fl ashes:
indication of tripping delay
of the corresponding threshold
Yellow LED ON/OFF:
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position:
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position:
any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque:
IP rating IP20
Tightening torque:
max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² fl exible without multicore cable end
5. Input circuit
Supply voltage:
12 to 400V AC
terminals A1-A2 (galvanically separated)
selectable via power modules TR2
Tolerance:
according to specifi cation
of power module
Rated frequency:
according to specifi cation
of power module
Rated consumption:
2VA (1.5W)
Duration of operation:
100%
Reset time:
500ms
Residual ripple for DC: -
Drop-out voltage:
Drop-out voltage:
>30% of the supply voltage
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
6. Output circuit
1 potential free change-over contact
Rated voltage:
Rated voltage:
250V AC
Switching capacity (distance <5mm):
750VA (3A / 250V AC)
Switching capacity (distance >5mm):
1250VA (5A / 250V AC)
Fusing:
5A fast acting
Mechanical life:
20 x 10
6
operations
Electrical life:
2 x 10
5
operations
at 1000VA resistive load
Switching frequency:
max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
7. Measuring circuit
Fusing:
max. 20A (according to UL 508)
Measured variable:
AC Sinus (48 to 63Hz)
Input:
3(N)~ 115/66V
terminals (N)-L1-L2-L3 (G2PM115VSY10)
3(N)~ 230/132V
terminals (N)-L1-L2-L3 (G2PM230VSY10)
3(N)~ 400/230V
terminals (N)-L1-L2-L3 (G2PM400VSY10)
Overload capacity:
3(N)~
3(N)~
115/66V 3(N)~173/100V
(G2PM115VSY10)
3(N)~
230/132V 3(N)~345/199V
(G2PM230VSY10)
3(N)~
400/230V 3(N)~600/346V
(G2PM400VSY10)
Input resistance:
3(N)~
3(N)~
115/66V 220k
Ω (G2PM115VSY10)
3(N)~
230/132V 470k
Ω (G2PM230VSY10)
3(N)~
400/230V 1M
Ω (G2PM400VSY10)
Switching threshold
Max:
-20% to +30% of U
N
Min:
-30% to +20% of U
N
Asymmetry:
5% to 25%
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
8. Accuracy
Base accuracy:
±5% (of maximum scale value)
Frequency response:
-
Adjustment accuracy:
≤5% (of maximum scale value)
Repetition accuracy:
≤2%
Voltage infl uence:
≤0.5%
Temperature infl uence:
≤0.1% / °C
9. Ambient conditions
Ambient temperature:
-25 to +55°C (according to IEC 68-1)
-25 to +40°C (according to UL 508)
Storage temperature:
-25 to +70°C
Transport temperature:
-25 to +70°C
Relative humidity:
15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree:
3 (according to IEC 60664-1)
Vibration resistance:
10 to 55Hz 0.35mm
(according to IEC 68-2-6)
Shock resistance:
15g 11ms (according to IEC 68-2-27)
G2PM...SY10