Tele 2390500 G2PM400VSY10 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 2390500 Scheda Tecnica

Codici prodotto
2390500
Pagina di 4
Subject to alterations and errors
Release 08/05
Monitoring relays - GAMMA series
Voltage monitoring in 3-phase mains
Multifunction
Monitoring of phase sequence and phase failure
Monitoring of asymmetry selectable
Connection of neutral wire optional
Detection of loss of neutral wire
Supply voltage selectable via power modules
1 change-over contact
Width 22.5mm
Industrial design
Technical data
1. Functions
Voltage monitoring in 3-phase mains with adjustable thresholds, 
adjustable tripping delay, monitoring of phase sequence and phase 
failure, monitoring of asymmetry with adjustable threshold and the 
following functions (selectable by means of rotary switch)
UNDER Undervoltage 
monitoring
UNDER+SEQ  Undervoltage monitoring and
 
monitoring of phase sequence
WIN 
Monitoring of window between Min and Max
WIN+SEQ 
Monitoring the window between Min and Max 
 
and monitoring of phase sequence
2. Time ranges
 Adjustment 
range
Start-up suppression time: 
-
Tripping delay: 
0.1s 
10s
3. Indicators
Red LED ON/OFF: 
indication of failure
 
of the corresponding threshold
Red LED fl ashes: 
indication of tripping delay
 
of the corresponding threshold
Yellow LED ON/OFF: 
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² fl exible without multicore cable end
5. Input circuit
Supply voltage:
 
12 to 400V AC 
terminals A1-A2 (galvanically separated)
 
 
selectable via power modules TR2
Tolerance: 
according to specifi cation
 
 
of power module
Rated frequency: 
according to specifi cation
 
 
of power module
Rated consumption: 
2VA (1.5W)
Duration of operation: 
100%
Reset time: 
500ms
Residual ripple for DC:  -
Drop-out voltage: 
>30% of the supply voltage
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
6. Output circuit
1 potential free change-over contact
Rated voltage: 
250V AC
Switching capacity (distance <5mm): 
750VA (3A / 250V AC)
Switching capacity (distance >5mm): 
1250VA (5A / 250V AC)
Fusing: 
5A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
7. Measuring circuit
Fusing: 
max. 20A (according to UL 508)
Measured variable: 
AC Sinus (48 to 63Hz)
Input:
 
3(N)~ 115/66V 
terminals (N)-L1-L2-L3  (G2PM115VSY10)
 
3(N)~ 230/132V 
terminals (N)-L1-L2-L3  (G2PM230VSY10)
 
3(N)~ 400/230V 
terminals (N)-L1-L2-L3  (G2PM400VSY10)
Overload capacity:
 3(N)~ 
115/66V  3(N)~173/100V 
(G2PM115VSY10)
 3(N)~ 
230/132V  3(N)~345/199V 
(G2PM230VSY10)
 3(N)~ 
400/230V  3(N)~600/346V 
(G2PM400VSY10)
Input resistance:
 3(N)~ 
115/66V  220k
Ω (G2PM115VSY10)
 3(N)~ 
230/132V  470k
Ω (G2PM230VSY10)
 3(N)~ 
400/230V  1M
Ω (G2PM400VSY10)
Switching threshold
 
Max: 
-20% to +30% of U
N
 
Min: 
-30% to +20% of U
N
Asymmetry: 
5% to 25%
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
8. Accuracy
Base accuracy: 
±5% (of maximum scale value)
Frequency response: 
-
Adjustment accuracy: 
≤5% (of maximum scale value)
Repetition accuracy: 
≤2%
Voltage infl uence: 
≤0.5%
Temperature infl uence: 
≤0.1% / °C
9. Ambient conditions
Ambient temperature: 
-25 to +55°C (according to IEC 68-1)
 
-25 to +40°C (according to UL 508)
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 class 3K3)
Pollution degree: 
3 (according to IEC 60664-1)
Vibration resistance: 
10 to 55Hz 0.35mm 
 
(according to IEC 68-2-6)
Shock resistance: 
15g 11ms (according to IEC 68-2-27)
G2PM...SY10