Tele 1340102 E1UU230V01 Gamma 1-Phase Voltage Monitoring Relay 1-phase voltage monitoring 1340102 Hoja De Datos
Los códigos de productos
1340102
Subject to alterations and errors
Release 10/06
Monitoring relays - ENYA series
AC/DC voltage monitoring in 1-phase mains
Undervoltage monitoring
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
AC/DC undervoltage monitoring in 1-phase mains with adjustable thres-
hold and fi xed hysteresis.
hold and fi xed hysteresis.
UNDER
Undervoltage
monitoring
2. Time ranges
Adjustment
range
Tripping delay (Delay):
-
3. Indicators
Green LED ON/OFF:
indication of supply voltage
Yellow LED ON/OFF:
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN rail TS 35 according to EN 50022
Mounting position:
Mounted on DIN rail TS 35 according to EN 50022
Mounting position:
any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque:
IP rating IP20
Tightening torque:
max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage:
(= measuring voltage)
Terminals:
230V AC
230V AC
E-F3
24V AC
E-F2 (distance > 5mm)
24V DC
E-F1(+)
Rated voltage Un:
see table ordering information or
printing on the unit
Tolerance:
-25% to +20% of Un
Rated consumption:
230V AC
230V AC
10VA (0.6W)
24V AC
1.3VA (0.8W)
24V DC
0.6W
Rated frequency:
AC 48 to 63Hz
Duration of operation:
100%
Reset time:
500ms
Wave form:
DC, AC Sinus
Hold-up time:
-
Drop-out voltage:
>60% of supply voltage
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
6. Output circuit
1 potential free change over contact
Rated voltage:
Rated voltage:
250V AC
Switching capacity:
1250VA (5A / 250V)
Fusing:
5A fast acting
Mechanical life:
20 x 10
6
operations
Electrical life:
2 x 10
5
operations
at 1000VA resistive load
Switching frequency:
max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
Overvoltage category:
III. (according to IEC 60664-1)
Rated surge voltage:
4kV
7. Measuring circuit
Measuring variable:
DC or AC Sinus, 48 to 63Hz
Measuring input:
(= supply voltage)
Terminals:
230V AC
230V AC
E-F3
24V AC
E-F2 Distance between the devices
musst be greater than 5mm!
24V DC
E-F1(+)
Overload capacity:
120% of Un
Input resistance:
-
Switching threshold Us:
see table ordering information or
printing on the unit
Hysteresis H:
see table ordering information or
printing on the unit
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
8. Accuracy
Base accuracy:
±5% of rated value
Adjustment accuracy:
±5% of rated value
Repetition accuracy:
≤2% of rated value
Voltage influence:
-
Temperature influence:
0,05% / °C
9. Ambient conditions
Ambient temperature:
-25 to +55°C (according to IEC 68-1)
Storage temperature:
-25 to +70°C
Transport temperature:
-25 to +70°C
Relative humidity:
15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree:
2, if built in 3
(according to IEC 664-1)
Vibration resistance:
10 to 55 Hz 0.35mm
(according to IEC 68-2-6)
Shock resistance:
15g 11ms
(according to IEC 68-2-27)
10. Weight
Single packing:
74g
Package of 10pcs:
676g per Package
E1UU