Tele 1340102 E1UU230V01 Gamma 1-Phase Voltage Monitoring Relay 1-phase voltage monitoring 1340102 Scheda Tecnica

Codici prodotto
1340102
Pagina di 2
Subject to alterations and errors
Release 10/06
Monitoring relays - ENYA series
AC/DC voltage monitoring in 1-phase mains
Undervoltage monitoring
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
AC/DC undervoltage monitoring in 1-phase mains with adjustable thres-
hold and fi xed hysteresis.
UNDER  
Undervoltage 
monitoring
2. Time ranges
  
 
Adjustment 
range
Tripping delay (Delay):   
             -
3. Indicators
     Green LED ON/OFF:   
indication of supply voltage
     Yellow LED ON/OFF:   
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required), 
IP rating IP20
Tightening torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage: 
(= measuring voltage)
Terminals: 
          230V AC 
E-F3
          24V AC 
E-F2   (distance > 5mm)
          24V DC 
E-F1(+)
Rated voltage Un: 
see table ordering information or
 
printing on the unit
Tolerance: 
-25% to +20% of Un
Rated consumption: 
          230V AC 
10VA (0.6W)
          24V AC 
1.3VA (0.8W)
          24V DC 
0.6W
Rated frequency: 
AC 48 to 63Hz
Duration of operation: 
100%
Reset time: 
500ms
Wave form: 
DC, AC Sinus
Hold-up time: 
-
Drop-out voltage: 
>60% of supply voltage
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
6. Output circuit
1 potential free change over contact
Rated voltage: 
250V AC
Switching capacity: 
1250VA (5A / 250V)
Fusing: 
5A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Overvoltage category: 
III. (according to IEC 60664-1)
Rated surge voltage: 
4kV
7. Measuring circuit
Measuring variable: 
DC or AC Sinus, 48 to 63Hz
Measuring input: 
(= supply voltage)
Terminals: 
          230V AC 
E-F3
          24V AC 
E-F2   Distance between the devices  
 
 
musst be greater than 5mm!
          24V DC 
E-F1(+)
Overload capacity: 
120% of Un
Input resistance: 
-
Switching threshold Us: 
see table ordering information or
 
printing on the unit
Hysteresis H: 
see table ordering information or
 
printing on the unit
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
8. Accuracy
Base accuracy: 
±5% of rated value
Adjustment accuracy: 
±5% of rated value
Repetition accuracy: 
≤2% of rated value
Voltage influence: 
-
Temperature influence: 
0,05% / °C
9. Ambient conditions
Ambient temperature: 
-25 to +55°C (according to IEC 68-1)
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 class 3K3)
Pollution degree: 
2, if built in 3
 
(according to IEC 664-1)
Vibration resistance: 
10 to 55 Hz 0.35mm
 
(according to IEC 68-2-6)
Shock resistance: 
15g 11ms
 
(according to IEC 68-2-27)
10. Weight
Single packing: 
 
74g
Package of 10pcs:   
676g per Package
E1UU