9. Technical Data
9.1 Max. permissible Load acc. to EN60669-2-1
9.2 Max. DC Load Breaking Capacity
DC breaking capacity
of 789-601
DC breaking capacity
of 789-602
Des ign ation
Item-no.
789-601
789-602
Supply voltage
Current consumtion (internal)
No. of  channels / outputs
No. Of receive-channels
Max sw itching f requency.
Delay-time ( Transmitter / 
ouput command)
Type of  contacts
NO contac ts
CO contacts
Sw itching voltage
Fusing of  Loads
Output current (per Channel)
max. 16A, A C1
max. 8A , A C1
Type of  load
Potential bonding
       Supply / Atenna
       Supply / Contac ts
       Channel / Channel
       Open Contacts
A mbient temperature
Storage temperature
Relative humidity
Degree of  pollution
Degree of  protection
Mounting position
Terminals
Stripping length
Housing
Mounting
Dimensions (w  x h x d)
A pprovals
40 / 10 per output
Modular Installation Housing
5 Hz
< 100ms
typ. 40...70ms
Wire breaker; max . 16A
DIN Rail  acc. EN 50022
230V ~
KEMA; acc. EN 60669-2-1:1996
2
IP20
-
4 kV ef f .
2,2 kV ef f .
1 kV ef f .
0 ... +55°C
appr. 70 x 90 x 55 mm
Data
5 - 6 mm
optional
WAGO CA GE-CLA MP (R)  Series 236 
-25 ... + 85°C
85% w ithout condensation
see table 8.1
DC24V  –15/+20%
Max. 90mA
4
9.3 Data Processing of PTM / STM Data
The  Radio Receiver is analyzing binary data from different 
types of radio transmitters which are based on the EnOcean
Radio Techno-logy. From following type of modules data could 
be processed:
Module type EnOcean
Application
PTM 100, 200, 230
push-buttons
STM250
window-contacts
STM100
industrial sensors / switches
From the data telegrams the following bits are used:
10. Accessories
Antenna: 
WAGO 758-910 incl. 2.5 m RG174-cable and SMA-
Connector.
11. General Advices for EnOcean Radio Technology
11.1 Safety Advices conc. R&TTE: Danger
The radio receiver modules must not be used in any 
relation with equipment that supports, directly or 
indirectly, human health or life or with applications 
that can result in danger for people, animals or real 
value.
This results from the classification of the radio receiver module 
in “Class 2 Equipment”according to ETSI EN 301 489-3 V1.4.1 
(2202-08) "Specific conditions for short-range devices (SRD)".
11.2 Details for Transmission Range
The transmission ranges are mainly depending on mounting 
and  positioning  as well as type of material which is used in 
buildings. The type of used materials  and thickness of walls 
have a main influence to the quality and the strength of radio 
data. 
It is recommended to make tests of data transmission at 
desired mounting positions before installation.
11.3 Typical max. Transmission Ranges
1) Visual contacts:  typ. 30 m in passages, up to 100 m in halls
2) Rigypsum walls/ wood: typ. 30 m range through max. 5 walls
3) Brick wall /Gas concrete: typ. 20 m range through max. 3 
walls
4) reinforceds concrete /-ceiling: typ. 10 m range through max. 1 
wall
Supply blocks and lift shafts should be seen as a 
compartmentalisation.
11.4 Reduction of Transmission Range
Restriction of the transmission range can also be due to:
•Hollow lightweight walls with insulating wool on metal foil
•suspend ceilings with panels made of metal
•carbon fiber, lead glass or glass with metal coating, metal 
furniture 
•metal wall mounting of the switch. 
In addition, the angle with which the signal arrives at the wall is 
of great importance. Depending on the angle, the effective wall 
strength and thus the damping attenuation of the signal 
changes. If possible, the signals should run vertically through 
the walling. Walling recesses should be avoided. 
For mounting and installation of transmitters please 
observe additionally the advices provided by the 
manufacturer!
Des.
Org- 
Data-
EnOcean Byte  Typ  Byte  Bit
PTM100
5
RPS
3
4...7
PTM200
5
RPS
3
4...7
PTM230
5
RPS
3
4...7
STM100
7
4BS
0
0
STM250
6
1BS
3
0
Type of load 
789-601
789-602
halogen lamps
1400W
1400W
incandescent lamps
2200W
1840W
iron-core transformer
120VA
120VA
fluorescent lamps 
4AX 
-
capazitive loads 
60µF
-
motorload
2A
2A
Product Type