Burnham Series 8H/8HE Boiler Hoja De Especificaciones

Descargar
Página de 4
(This is standard on 805, 808-810, optional on 806-807) 
(This ignition system must be used only with gas control train Option b.) 
 
               of the EI type electronic control system which shall provide an electrically ignited intermittent gas pilot   
 
             and permit the main gas valve to open only when the pilot burner is proven to be lit.  Should a loss of pilot  
 
             flame occur, the main  gas valve will close and the spark will recur within 0.8 seconds.  If pilot fails to      
 
             ignite within 90 seconds, control will attempt to relight after 5 minutes.  System shall include an electronic 
 
             ignition module, pilot assembly, and pilot gas valve. 
 
Option (c) 
(This ignition system must be used only with gas control train Option a.) 
 
             of the OP type electronic control system which provides manual ignition of electronic pilot assembly,       
 
           100% shut-off constant burning pilot, electronic supervision of pilot flame, 0.8 second flame response        
 
            time, 30 second safety switch timing and shall include (1) factory pre-wired electronic control panel           
 
           including: Honeywell RM7890C relay module, main power on switch and light, gas valve on switch and     
 
           light, alarm light to indicate flame failure and terminal strip. 
Option (d) 
(This ignition system must be used only with gas control train Option a.) 
 
             of the EP type electronic control system which provides electric ignition, 100%  shut-off, intermittent pilot  
 
              flame operation, electronic supervision of the pilot flame, 0.8 second flame response time, 30 second        
 
             safety switch timing, and shall include (1) factory-prewired electronic control panel including:  Honeywell  
 
             RM7890A relay module, main power on switch and light, gas valve on switch and light, alarm light to      
 
             indicate flame failure and terminal strip. 
Option (e) 
(This ignition system must be used only with gas control train Option c.) 
 
             of the OP-IRI type electronic control system which provides manual ignition of electronic pilot assembly,  
 
           100% shut-off constant burning pilot, electronic supervision of pilot flame, 0.8 second flame response        
 
           time, 30 second safety switch timing and shall include (1) factory pre-wired electronic control panel           
 
            including: Honeywell RM7890C relay module, main power on switch and light, gas valve on switch and     
 
           light, alarm light to indicate flame failure, alarm bell, silencing switch, and terminal strip. 
 
Option (f) 
(This ignition system must be used only with gas control train Option c.) 
 
             of the EP-IRI type electronic control system which provides electric ignition, 100% shut-off, intermittent   
 
           pilot flame operation, electronic supervision of the pilot flame, 0.8 second flame response time, 30 second   
 
           safety switch timing, and shall include (1) factory-prewired electronic control panel including:  Honeywell   
 
            RM7890A relay module, main power on switch and light, gas valve on switch and light, alarm light to        
 
           indicate flame failure, alarm bell, silencing switch, and terminal strip. 
5.  MULTIPLE BOILER EQUIPMENT AND CONTROL SYSTEM 
 
*5.1 
Factory fabricated water manifolds shall be provided that are designed for primary/secondary circulation.     
 
    
One combination supply and return manifold with interconnecting boiler-to-manifold piping shall be           
 
   
 installed by the contractor. 
 
*5.2 
Factory fabricated water manifolds shall be provided that are designed for parallel supply and return           
 
   
circulation.  One set of supply and return manifolds with interconnecting boiler-to-manifold piping shall be   
 
   
installed by the contractor. 
 
  5.3 
The manifolds shall be furnished with two three-quarter inch tappings for gauges or controls and have lateral  
 
   
 connections that can be used with union connectors or flexible couplings. 
 
  5.4 
Contractor shall furnish and install a multiple boiler control system to step fire boilers as needed to meet      
 
   
system demand.  (select option a, b, c, d, e, f, or g):