Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Installing a Liebert iCOM Unit-to-Unit Network
Liebert
®
 iCOM
®
94
Large Displays
A network switch is required to enable Ethernet communication on one or more cooling units with 
large displays. Each cooling unit with a large display requires two straight-through Ethernet cables 
from a network switch. One cable connects to port P64 on the Liebert iCOM input/output board and 
the other straight-through cable connects to the female-female coupler, if the female-to-female 
coupler is provided with the unit. Connect the red crossover cable, which is provided with the cooling 
unit, between the coupler and the P64 port on the back of the large display (see Figure 81). If the 
female-to-female coupler is not provided, connect the straight-through cable to Port P64 on the large 
display.
Figure 78 U2U network setup diagram
NOTE
A female-to-female coupler is factory-supplied on some cooling units equipped with a large 
display.
NOTE
The first three octets of the units’ IP addresses must match for proper communication. In the 
illustration above, these are the matching octets: 192.168.254
Network
Switch
Liebert Cooling Unit 
with Small Liebert 
iCOM Display
Liebert Cooling Unit 
with Small Liebert 
iCOM Display
Liebert Cooling Unit 
with Large Liebert 
iCOM Display
Display Service/Network
Liebert iCom Display Menu
IP Address: 192.168.254.001
U2U Address: 33
Group #: 1
---------------------------------------
Display Service/Network
Liebert Cooling Unit 
Control Board Menu
IP Address: 192.168.001.002
U2U Address: 1
Group #: 1
Display Service/Network
Liebert Cooling Unit
Control Board Menu
IP Address: 192.168.254.003
U2U Address: 2
Group #: 1
Display Service/Network
Liebert Cooling Unit
Control Board Menu
IP Address: 192.168.254.004
U2U Address: 3
Group #: 1