Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Installing a Liebert iCOM Unit-to-Unit Network
95
Liebert
®
 iCOM
®
Wall-Mount Large Display
Only large displays can be used for remotely monitoring and controlling cooling units connected on 
the same network. Each wall-mount large display requires 120VAC or 230VAC input power; 
Emerson
®
 provides an AC adapter wall plug. A straight-through Ethernet cable must be connected 
between the network switch and the P64 port on the back of the display. This will enable control and 
monitoring capabilities to any cooling unit connected to the network.
Combining Large and Small Displays on a U2U Network
Setting up a network of cooling units equipped with large and small displays requires a network 
switch. The controls are to be connected to the switch as described above.
Figure 79 Wiring a small display for stand-alone operation
Small Graphics Display
CANbus Cable
P66 P67
CAN CAN
Liebert iCOM
Control Board