User Menu Parameters
Liebert
®
 iCOM
®
112
Figure 95 Sensor data screen, page 3
U325 Remote / Auxiliary Sensors - Unit Information—read only text describing screen features.
U326 REM Sensors set to Control—Read-only parameter that shows the number of sensor set to 
control (left hand value) and the sensor control type used (right hand value). If the sensors are used 
for reference only, the right hand value will display None. Otherwise the right hand value will display 
the sensor control mode such as Cool, Fan or Cool + Fan.
U327 Unit Aggregation Method—Read=only parameter that describes the sensor level control or 
aggregation method used for control. The left hand value will display Maximum or Average of based 
on the Service Menus>Remote SB03 programming. If set to Average, a number will appear to the 
right. This number represents the highest number of remote sensors used for calculating the average 
temperature. This number is also based on the programming in Service Menus>Remote SB0.3.
U328 Remote Sensor 1/2—Displays the actual remote sensor reading for each remote sensor. The 
actual value reported here depends on how the sensor is set up. If the sensor is set to Average, then an 
average of the two temperature readings per sensor will be shown. If the sensor is set to Maximum
then the maximum value will be shown.
U329 Remote Sensor 3/4—Same as Remote Sensor 1/2
U330 Remote Sensor 5/6—Same as Remote Sensor 1/2
U331 Remote Sensor 7/8—Same as Remote Sensor 1/2
U332 Remote Sensor 9/10—Same as Remote Sensor 1/2
U333 Remote Sensor Unit Average—Displays the average remote sensor temperature taken from 
the total number of remote sensor readings above. 
U334 Remote Sensor Unit Maximum—Displays the maximum remote sensor temperature taken 
from the remote sensor readings above.
U336 Unit Aggregated Ctrl Temperature—Displays the remote sensor temperature control 
temperature when cooling or fans are set to control based off remote temperature.