Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
User Menu Parameters
113
Liebert
®
 iCOM
®
Figure 96 Sensor data screen, page 4
U337 Remote / Auxiliary Sensors - System Information—Read-only text describing screen 
features.
U338 Teamwork Mode—Read-only parameter describes what U2U teamwork mode the unit is 
operating in.
U339 Teamwork Aggregation Method—Read-only parameter is viewable only in Teamwork 1 and 
3 with temperature or fan control sensor set to Remote. This parameter describes if the teamwork 
control is based on the average or maximum sensor readings in the group. If programmed to Average
the parameter will also display how many units are calculated in the average. Only the highest sensor 
readings will be used for the averaging. 
U341 System Remote Sensor Average—Read-only parameter is viewable only in Teamwork 1 and 
3 with temperature or fan control sensor set to Remote. This parameter displays the average remote 
sensor reading of all connected sensors.
U342 System Remote Sensor Maximum—Read-only parameter is viewable only in Teamwork 1 
and 3 with temperature or fan control sensor set to Remote. This parameter displays the average 
remote sensor reading.
U344 Aux Air Weight / Temp—Read-only parameter is viewable only when the unit is connected to 
wireless sensors, the unit is in Teamwork 1 or 3, temperature or fan control sensor set to Remote to 
view this parameter and teamwork is based on Average control. This parameter displays the weight 
applied to the wireless control (left hand value) and actual wireless sensor reading (right hand value). 
The left hand value represents the amount of influence the actual wireless sensor reading (right hand 
value) has relative other remote sensors for controlling component operation. The actual wireless 
sensor reading (right hand value) is the maximum or average wireless sensor reading transmitted 
from the auxiliary proxy or Liebert SiteLink
®
.
U345 Aux Air Mode / Temp—Read-only parameter is viewable only when the unit is connected to 
wireless sensors, the unit is in Teamwork 1 or 3, temperature or the fan control sensor set to 
Remote
 
and teamwork is based on Maximum. This parameter describes how the wireless sensors are used in 
the teamwork calculation (left hand value) and what the actual wireless sensor reading (right hand 
value). Three possible statuses may be shown as the left hand value: EXCL, INCL and ONLYEXCL 
indicates that the wireless sensor value is not used for determining the unit fan or cooling operation. 
INCL indicates the wireless sensor value is considered for controlling fan or cooling operation. ONLY 
indicates the wireless sensor value is used for determining fan or cooling operation. The actual 
wireless sensor reading (right hand value) is the maximum or average wireless sensor reading 
transmitted from the auxiliary proxy or Liebert SiteLink.
U348 System Aggregated Ctrl Temperature—Read-only parameter is control temperature for 
cooling or fan when the unit is in Teamwork 1 or 3.