Service Menu Parameters
Liebert
®
 iCOM
®
146
Figure 132
Diagnostics/service mode screen, page 6 of 8
S356 Status HP1—Shows the status of the unit’s Compressor 1 high-pressure switch input.
S357 Status LP1—Shows the status of the unit’s Compressor 1 low-pressure switch input.
S358 Status C1 OL—Shows the status of the unit’s Compressor 1 overload input.
S359 Status HP2—Shows the status of the unit’s Compressor 2 high-pressure switch input.
S360 Status LP2—Shows the status of the unit’s Compressor 2 low-pressure switch input.
S361 Status C2 OL—Shows the status of the unit’s Compressor 2 overload input.
Figure 133
Diagnostics/service mode screen, page 7 of 8
S367 Status Humidifier Problem—Shows the status of the high water level indicator on an 
infrared humidifier.
S368 Status DT1 (Outdoor/Glycol)—Indicates if the delta T between outdoor air ambient 
temperature and glycol fluid temperature has been met.
S369 Status DT2 (Glycol/Room)—Indicates if the delta T between glycol and room return air 
temperature has been met.