Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Service Menu Parameters
Liebert
®
 iCOM
®
148
Figure 135
Set alarms screen, page 1 of 11
S202 Return Sensor Alarms—Enables and disables the return temperature and humidity sensor 
alarms. Factory default is set to enable.
S203 High Return Temperature—Sets the threshold temperature when a return high 
temperature alarm will occur.
S204 Low Return Temperature—Sets the threshold temperature when a return low temperature 
alarm will occur.
S205 High Return Humidity—Sets the threshold humidity when a return high humidity alarm 
will occur.
S206 Low Return Humidity—Sets the threshold humidity when a return low humidity alarm will 
occur.
S207 Sensor A Alarms—Enables or disables the alarms associated with Sensor A if the unit is 
equipped with the optional temperature / humidity sensor.
S208 High Temperature Sensor A—Sets the threshold temperature when a Sensor A high 
temperature alarm will occur.
S209 Low Temperature Sensor A—Sets the threshold temperature when a Sensor A low 
temperature alarm will occur.
S210 High Humidity Sensor A—Sets the threshold humidity when a Sensor A humidity alarm will 
occur.
S211 Low Humidity Sensor A—Sets the threshold humidity when a Sensor A low humidity alarm 
will occur.
S21A Loss of Flow Compressor Timer—Allows setting a maximum pumpdown time during a loss 
of flow condition to prevent causing a high-pressure alarm due to pumpdown with no water/glycol 
flow to the condenser; hidden unless pumpdown is enabled; applies only to water-cooled systems.
S21B Loss of Flow CFC Threshold—Sets the threshold for CFC loss of flow.