Emerson Liebert iCOM Manual De Usuario
Service Menu Parameters
Liebert
®
iCOM
®
166
S6E9 Sensor_D R Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the right side of supply Sensor D to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6F1 Sensor_E L Offset / Read—The left hand parameter adjusts the thermistor temperature
S6F1 Sensor_E L Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the left side of supply Sensor E to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6F2 Sensor_E R Offset / Read—The left hand parameter adjusts the thermistor temperature
S6F2 Sensor_E R Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the right side of supply Sensor E to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
8.8
Service-Economizer Menu Screens
Economizer provides advanced air side Economizer monitoring and parameter adjustment
Figure 160
Economizer, page 1 of 3
SA02 Enable Economizer—Sets the Liebert Air Economizer
™
operation to one of the following
modes. These selections only determine if the Liebert Air Economizer is available for use; they do not
determine or override damper position. Damper position is always controlled by the sensor set to
control temperature (i.e., Return / Supply Sensor)
• Yes: This parameter will operate the Liebert Air Economizer based on the outdoor sensor reading
and will allow the Liebert iCOM to determine if the conditions are within the acceptable range of
operation.
• NO: This parameter will disable the Liebert Air Economizer and will not allow Liebert Air
Economizer to operate even if the outdoor conditions are acceptable.
• Remote: This parameter will enable the Liebert Air Economizer and ignore the outdoor Liebert
iCOM sensor even if the conditions are outside the range of operation.
SA04 Humidity Ratio—Sets the minimum and maximum limits of outdoor air based on the amount
of moisture content. The humidity ratio is set based on pounds of moisture per pound of dry air. This
is equivalent to the dew point temperatures.
SA05 Wet Bulb Temp—Read-only value that displays the outdoor wet bulb temperature. (This
SA05 Wet Bulb Temp—Read-only value that displays the outdoor wet bulb temperature. (This
reading will be in metric values.)
SA06 Outdoor Temp—Displays the actual outdoor temperature based on the Temperature
SA06 Outdoor Temp—Displays the actual outdoor temperature based on the Temperature
Humidity sensor (Sensor C). When this parameter shows OK, the outdoor temperature requirements
have been met to use economization. When NOK is shown, the outdoor temperature is outside the
operating range set in the Liebert iCOM control.