Service Menu Parameters
165
Liebert
®
iCOM
®
Figure 159
Sensor calibration/setup screen, page 12 of 12
S6D9 Supply Sensor NTC or PTC—Supports only the NTC selection.
S6E1 Supply NTC Offset / Read—The left hand parameter adjusts the supply temperature reading
S6E1 Supply NTC Offset / Read—The left hand parameter adjusts the supply temperature reading
from the actual sensor to compensate for any sensor error or to match other sensors in the conditioned
space. The right hand parameter shows the calibrated value in degrees Celsius or degrees
Fahrenheit.
S6E2 Sensor_A L Offset / Read—The left hand parameter adjusts the thermistor temperature
S6E2 Sensor_A L Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the left side of supply Sensor A to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6E3 Sensor_A R Offset / Read—The left hand parameter adjusts the thermistor temperature
S6E3 Sensor_A R Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the right side of supply Sensor A to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6E4 Sensor_B L Offset / Read—The left hand parameter adjusts the thermistor temperature
S6E4 Sensor_B L Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the left side of supply Sensor B to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6E5 Sensor_B R Offset / Read—The left hand parameter adjusts the thermistor temperature
S6E5 Sensor_B R Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the right side of supply Sensor B to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6E6 Sensor_C L Offset / Read—The left hand parameter adjusts the thermistor temperature
S6E6 Sensor_C L Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the left side of supply Sensor C to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6E7 Sensor_C R Offset / Read—The left hand parameter adjusts the thermistor temperature
S6E7 Sensor_C R Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the right side of supply Sensor C to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.
S6E8 Sensor_D L Offset / Read—The left hand parameter adjusts the thermistor temperature
S6E8 Sensor_D L Offset / Read—The left hand parameter adjusts the thermistor temperature
leaving the left side of supply Sensor D to compensate for any sensor error or to match other sensors
in the conditioned space. The right hand parameter shows the calibrated value in degrees Celsius or
degrees Fahrenheit.