Emerson Liebert iCOM Manual De Usuario
Service Menu Parameters
Liebert
®
iCOM
®
172
Figure 166
System/network setup screen—Unit, page 2 of 2
S835 Monitoring Protocol—Selects the monitoring protocol. Velocity V4 is the factory default that
will provide communication to the Liebert IntelliSlot
®
housing. IGMNet will activate the legacy
Liebert SiteLink
™
protocol for communication to the Liebert SiteLink
™
(-E). Liebert Hironet
™
is used
only on Liebert HPM
™
units.
S836 IP Address—Contains the network address of the display. This address must be unique on the
network.
S837 Netmask—Netmask is used to divide IP addresses in subnet and specify the network available
S837 Netmask—Netmask is used to divide IP addresses in subnet and specify the network available
to hosts.
S838 Gateway—Routes data and act as a proxy server or a firewall when setting up networks.
S839 MAC—Unique hardware identifier of the Ethernet device; read-only.
S840 U2U Protocol—This parameter is always set to GBP.
S841 U2U Address—Unique identifier for each unit on the network. Display addresses range from
S838 Gateway—Routes data and act as a proxy server or a firewall when setting up networks.
S839 MAC—Unique hardware identifier of the Ethernet device; read-only.
S840 U2U Protocol—This parameter is always set to GBP.
S841 U2U Address—Unique identifier for each unit on the network. Display addresses range from
33 to 64. Each display on the U2U network must have a different U2U address.
S842 U2U Group—Creates zones or groups within a U2U network. Once a group number is selected,
S842 U2U Group—Creates zones or groups within a U2U network. Once a group number is selected,
the display will see only devices with the same group number. The group number can be changed to
view other devices in different groups.
S843 Bootloader Variables—Indicates if there has been a change to the boot loader since it was
S843 Bootloader Variables—Indicates if there has been a change to the boot loader since it was
last loaded. This parameter should only be activated by an authorized service person.
S844 Static RAM—Static RAM shows the status of changes made and whether they have been saved
S844 Static RAM—Static RAM shows the status of changes made and whether they have been saved
to the Static Memory on the board. The ranges of this parameter are, 0=Not Available, 1=Invalid,
2=OK, 3=Changed, 4=Updating and 5=Locked. The right hand parameter will allow the user to do
two options, 0=nothing or 1=Clear+Reboot. This clears all the settings in the Static RAM.