Service Menu Parameters
Liebert
®
 iCOM
®
178
Figure 172
Options setup, page 6 of 6
S457 Q15 Output Function—Sets the output function for Q15. This parameter is selectable for 0 = 
None, 1 = Dehum On, 2 = Cooling On, 3 = Reheat On, 4 = Comp On, 5 = Comp 1 On, 6 = Comp 2 On, 7 
= Humi On, 8 = Fan On, 9 = FreeCool On, 10 = Damper, 11 = High Temp, 12 = Low Temp, 13 = Loss 
Power and 14 = Power Source The factory default is none. NOTE: Unit Code 16 can set the output for 
this parameter. The Q15 output is rated up to 27VAC and 2A. An additional contactor or control relay 
with power supply will be required if the application exceeds this limit.
S458 Q15 output direction—Sets the Q15 output direction. This parameter is adjustable from 
direct or reverse. The factory default is direct.
S459 Fan delay for damper—Sets the delay for the damper to open before the fan starts. This 
parameter is adjustable from 0 to 120 seconds.
S460 Damper switch feedback damper—Sets the timer for the damper when using Q15. This 
parameter is adjustable from 0 to 120 seconds. The factory default is 30 seconds.
S461 Q15 Temp output sensor—This parameter is adjustable from 0 = Return, 1 = Supply, 
2 = Rem Max, 3 = Rem Low and 4 = Rem Avg. The factory default is Return.
S462 Q15 Temp output threshold—Sets the output threshold for the temperature using Q15. This 
parameter is adjustable from 32°F to 150°F. The factory default is 80°F.
S463 Q15 temp actual—Shows the status of the temperature in Celsius or Fahrenheit for Q15.
S465 Medium board: Q15 map to K11—Shows the status of Q15 being mapped to K11 on the 
medium board. This parameter will be shown as No or Yes. On the medium board, Q15 is mapped to 
K11 and is selectable. If this has been selected, this parameter will show the status of K11.
S466 Q15 output state—Shows the status of the Q15 output state. This parameter will be shown as 
Off or On.