Emerson Liebert iCOM Manual De Usuario
Operation
Liebert
®
iCOM
®
24
Pump Down
Pump down is applicable to compressorized systems that are equipped for pump-down operation,
which is set at the factory. This operation prevents the compressor oil from being diluted with liquid
refrigerant to ensure that the compressor is properly lubricated for the next startup. Systems
equipped with crankcase heaters and discharge line check valves may be set for pump down, however
it is not required.
The pump down operation operates in the following manner:
Whenever the control determines that no more cooling is required and a compressor should be shut
The pump down operation operates in the following manner:
Whenever the control determines that no more cooling is required and a compressor should be shut
Off, the liquid line solenoid valve (LLSV) is closed (de-energized). The compressor will continue to
operate until the low suction pressure device (LPS or LPT) opens, which shuts Off the compressor. If
the LP device does not open within a specified time, the LLSV is turned On, then back Off (the
assumption is that the LLSV is stuck). If, after three times, the LP device does not open, the
compressor and LLSV are locked Off and an alarm “Pump Down not completed” will appear.
There is a re-pump down if the LP device opens again after the compressor has been already
There is a re-pump down if the LP device opens again after the compressor has been already
stopped—a maximum of six re-pump-down cycles per hour are allowed. At the seventh request of
re-pump down, the alarm “Comp 1 Pumpdown Fail” or “Comp 2 Pumpdown Fail” will appear and the
compressor will be locked out.
Pump down is always performed loaded (for compressors with unloaders: unloaders Off, digital scroll:
Pump down is always performed loaded (for compressors with unloaders: unloaders Off, digital scroll:
control solenoid valve disabled).
For digital scroll only: when pump down has finished successfully (LP device opened), pump down will
For digital scroll only: when pump down has finished successfully (LP device opened), pump down will
be continued for another half-second with the control solenoid valve energized.
High-Pressure Alarm
When the compressor is initially activated, the system will be monitored for a high-pressure situation.
When high-pressure is detected during the first 10 minutes of operation, the unit will attempt to
correct the problem several times without notification. If the unit is unsuccessful in correcting the
problem, an alarm will occur and the affected compressor will be locked Off. If high head pressure
alarm trips three times in a rolling 12 hour period, the affected compressor will be locked Off.
After the compressor has been running for 10 minutes, if a high head pressure situation is detected,
After the compressor has been running for 10 minutes, if a high head pressure situation is detected,
an alarm will occur and the affected compressor will be immediately locked Off without the unit
trying to correct the problem.
Once the compressor is locked Off, it will not come back On until main power is reset or until the
Once the compressor is locked Off, it will not come back On until main power is reset or until the
HP Alarm Counters (Service Menu, Diagnostics) are reset to 0.
Figure 22 Diagnostics/service mode screen, page 1 of 8
NOTE
The pump down function is not available on all units. Emerson removed pump down control
The pump down function is not available on all units. Emerson removed pump down control
from Thermal Management products in 2011. Units shipped in 2011 and before may have
pump down enabled.
HP Alarm Counters