Operation
Liebert
®
 iCOM
®
26
3.1.7 Compressor Sequencing on Two-Compressor Units
Compressor Sequencing parameter (Service Menu, Options Setup) is intended to maintain equal run 
times between compressors. This setting has three selection possibilities:
• Always use Compressor 1 as lead compressor.
• Always use Compressor 2 as lead compressor.
• Auto:
• First priority: if the safety timings are acceptable for only one compressor, then it is the next 
to be started/stopped.
• If both compressors are Off: the one with fewer working hours is the next to start.
• If both compressors are in operation: the one that has been operating longer since the last 
start is the next to be stopped.
3.1.8 Motorized Ball Valve in Water-Cooled Units
On water/glycol-cooled units with digital scroll compressors), pressure changes during each digital 
cycle during unloaded operation. This rapid pressure change would cause a conventional water 
regulating valve to open and close an excessive number of times.
Excessive valve cycling is avoided on units with digital scroll compressors) by monitoring a liquid line 
transducer and regulating heat exchanger fluid flow with a motorized ball valve (MBV). The control 
algorithm for the motorized ball valve uses an intelligent sampling rate and adjustable pressure 
threshold (S427 Ball Valve Setpoint Offset in Figure 169) to reduce the number of times the valve 
opens and closes. System reliability and performance is enhanced using a brass valve, linkage and 
actuator.
Each compressor has one motorized ball valve that is driven by the analog output of the Liebert iCOM 
based on discharge pressure. If there is a call for cooling, the compressor start is delayed by a 
30-second timer. During this delay, the motorized ball valve is set to 50% open to allow fluid flow 
through the unit condenser. The compressor will start after the 30-second timer elapses.
Motorized Ball Valve Manual Mode: (Service/Service, Figure 130) Manual operation can be 
selected to allow service personnel to control the motorized ball valve from the Liebert iCOM.
 When Auto BV Control is selected, the motorized ball valve functions as it would be during normal 
system operation.
When Manual BV Control is selected, the user must be careful in setting the MBV position because 
the ball valves will remain in the position set in the Service menu until the control is switched back to 
Auto or until a technician changes the valves to another manual position (the motorized ball valve in 
manual mode can be set in 1% increments from fully closed to fully open). Low or high discharge 
pressure may occur during this mode, depending on environmental conditions and the position of the 
motorized ball valve.
The motorized ball valve is driven by a 2-10VDC proportional control signal: the valve is closed at 
2VDC, 50% open at 6VDC and fully open at 10 VDC.
3.1.9 MBV Operation After Compressor is Turned Off
Once a compressor has stopped, the MBV control will continue to change the MBV position to 
maintain system pressures for a maximum time of 10 minutes by following the Auto BV control 
algorithm. When the 10-minute delay has expired or the discharge pressure is below its minimum 
threshold, the motorized ball valve will close until the next compressor activation.
NOTE
The Auto setting attempts to maintain equal run times between compressors. However, 
the control will not turn Off a compressor to equalize run time when it is needed to 
control the space.
 NOTE
Compressor operation will be delayed 30 seconds to allow the motorized ball valve to position 
itself for initial startup.