Emerson Liebert iCOM Manual De Usuario
Teamwork
Liebert
®
iCOM
®
78
4.2.1 Application of Teamwork Modes
All units in a network will run in the same Teamwork Mode.
• No Teamwork: Multiple zones in one room
• Teamwork Mode 1: Balanced load (small groups of units inside the same environment)
• Teamwork Mode 2: Unbalanced load (large rooms, not all units will have the same load) (work
• Teamwork Mode 1: Balanced load (small groups of units inside the same environment)
• Teamwork Mode 2: Unbalanced load (large rooms, not all units will have the same load) (work
well for most applications)
• Teamwork Mode 3: Allows the cooling capacity (Supply Sensor) to operate as a local control by
removing only the amount of load required to maintain the discharge air temperature at each
unit. This allows for an unbalanced room load while maintaining a consistent discharge air
temperature. The fan speed is controlled by the remote rack sensors (return, supply, under floor
static pressure) of all units, providing a controlled delivery method of the air to the cold aisle. In
raised floor applications, Liebert iCOM units will share sensor information to achieve even
under-floor air distribution. This distribution is achieved by operating all fans in parallel, which
will also yield the greatest energy efficiency.
4.2.2 No Teamwork
All cooling units work independently, responding to their own sensors. Standby function and unit
rotation are possible, but cascading is not (see Standby and Cascade on page 90). Autoset will not
adjust the proportional band in this mode.
4.2.3 Teamwork Mode 1
Teamwork Mode 1 works best in small rooms with balanced heat loads. The return temperature and
humidity sensor readings of all units in operation (fan on) are averaged by the master unit, Unit #1,
and used for control. The master unit will send the operating requirements to all operating units
according to unit numbers, rotated by one unit every 24 hours.
In this teamwork mode, most of the parameters are shared; if set in any one of the units, all other
In this teamwork mode, most of the parameters are shared; if set in any one of the units, all other
units will follow with the same settings. AutoSet will adjust the proportional band in Teamwork
Mode 1, see 3.3 - Temperature Control.
The master unit evenly divides the system proportional band among the number of available units.
The master unit evenly divides the system proportional band among the number of available units.
Each unit will receive instruction on how to operate from the master unit based on how far the system
deviates from the setpoints.
The number of available units is calculated like:
The number of available units is calculated like:
• In non-standby configuration: all units with fan on
• In typical standby function (no cascade): all units with fan on
• In cascade mode: all units that could operate (no alarm, which forces the unit to switch Off, unit
• In typical standby function (no cascade): all units with fan on
• In cascade mode: all units that could operate (no alarm, which forces the unit to switch Off, unit
not switched Off, etc.)
Figure 64 shows how two cooling units work together in Teamwork Mode 1,staging compressors
serially. Since Unit 1 and Unit 2 are available to operate, the master unit, Unit 1, collects the average
or maximum (based on S804 “Teamwork is based on” programming) temperature and humidity
sensor readings from each unit. Settings in S804 “Teamwork is based on” programming determines
whether the unit uses the average or maximum temperature and humidity sensor.
NOTE
1. Proportional actuators (chilled water valves and free-cooling valves) are driven in parallel.
2. Dual-cool and free-cooling units cannot be set in Teamwork 1 if compressors and
1. Proportional actuators (chilled water valves and free-cooling valves) are driven in parallel.
2. Dual-cool and free-cooling units cannot be set in Teamwork 1 if compressors and
free-cooling valves are set for simultaneous operation.
3. On free-cooling or dual-cool units where simultaneous operation is set to No, chilled water
valves ramp in parallel. If free-cooling is not possible for one unit, the group will switch to
compressor operation. Compressor staging may work serially or in parallel depending on
compressor type. See below for compressor ramping.
• The compressors will ramp in parallel if all units in the group are digital scroll.
• Compressor staging will be done serially if all the units in the group are four-step, two-
• Compressor staging will be done serially if all the units in the group are four-step, two-
step semi-hermetic or standard scroll.
• Compressor staging will be done in parallel if there is a mix of digital scroll compressors
with four-step, two-step semi-hermetic or standard scroll.
4. Low limit and dehumidification are managed from each unit independently.