Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Teamwork
Liebert
®
 iCOM
®
80
4.2.5 Teamwork Mode 3 (Optimized Aisle)
Teamwork Mode 3 can be selected when the units are set to operate in Optimized Aisle Control mode 
and have been connected in a unit-to-unit network. Teamwork provides coordination between the 
units that will prevent “fighting” by not allowing units to operate in conflicting modes of operation at 
the same time by selecting which mode to operate within based on the average of the collective unit 
sensors (Cooling vs. Heating and Humidifying vs. Dehumidifying). For additional details, see 3.9 - 
Liebert Optimized Aisle Control.
Teamwork Mode 3 allows the cooling capacity (Supply Sensor) to operate as a local control by 
removing only the amount of load required to maintain the discharge air temperature at each unit. 
This allows for an unbalanced room load while maintaining a consistent discharge air temperature. 
The fan speed is controlled by the remote rack sensors of all units, providing a controlled delivery 
method of the air to the cold aisle. In raised floor applications, Liebert iCOM units will share sensor 
information to achieve even under-floor air distribution. This distribution is achieved by operating all 
fans in parallel, which will also yield the greatest energy efficiency.
Figure 65 shows the difference in both under-floor air distribution and energy consumption when 
Variable Fan speed and Teamwork Mode 3 are applied to the Liebert cooling units. The example on 
the left is using the standard standby configuration; the example on the right is utilizing Teamwork 
Mode 3. The units below are assuming that the fan power consumed at each unit is 8.1kW when 
operating at 100%.
Figure 65  Teamwork Mode 3—Fixed speed vs. variable speed
Cascade
When data center environments require the cooling equipment to modulate from very low loads to the 
full design load, iCOM can coordinate unit capacity and unit activation in accordance with the 
Teamwork Mode 3 operation described above. The Liebert iCOM optimized aisle controlled units that 
are placed into Standby mode will activate as the room environment demands more cooling capacity. 
iCOM will monitor the rack sensors and current operating state of each unit to determine when to 
activate a standby unit. 
To provide the most efficient operation from a system perspective, the Liebert iCOM will first ramp 
the operating units fans and chilled water valve to compensate for the increased heat load. Once the 
operating units have reached a set fan speed, the supply compensation (see Figure 107) may be 
activated to determine if a lower supply temperature can compensate for the load increase. Once the 
supply compensation routine has reached its threshold then the Liebert iCOM will activate a standby 
unit within the group.
C
R
A
C
Fixed Speed
Variable Speed
C
R
A
C
C
R
A
C
C
R
A
C
C
R
A
C
C
R
A
C
C
R
A
C
C
R
A
C
Area within dotted lines is 
being cooled by CRAC units 
controlled by Liebert iCOM
Three Units On—One Unit in Standby
Fans must operate at 100% to meet demand
3 Units x 8.1kWh = 24.3kW per hour
Four Units Operating Together
Fans can operate at 75% to meet demand
4 Units x 3.43kWh = 13.72kW per hour