Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Teamwork
83
Liebert
®
 iCOM
®
4.2.6 Hardware Setup
The Liebert Optimized Aisle Control requires:
• A temperature/humidity sensor in the cold aisle and connected to the Liebert iCOM via CANbus. 
This can be done by:
• Moving the return temperature sensor from the cooling unit to the cold aisle with a longer 
CANbus cable
—OR BY—
• Obtaining a remote temperature sensor and addressing it to operate as the return 
temperature sensor.
• An additional supply temperature sensor placed under the raised floor.
4.3
Liebert Optimized Aisle Rack Sensor Installation
Each 2T sensor has two wires leaving the housing with temperature sensors on the end of each wire; 
Figure 68 2T sensor
To install the Optimized Aisle Control 2T Sensor Array:
1. Set the DIP switch settings for the 2T sensors.
2. Terminate the final sensor on the CANbus link.
3. Install the 2T sensors on racks to be monitored.
4. Install the CANbus cable between 2T sensors.
5. Install the CANbus cable at the unit.
Figure 69 Setting DIP switches for 2T sensors
Sensors shown may 
differ depending on 
equipment installed
2T Sensor Housing 
(back)
Terminating
Jumper
2T Sensor Housing 
(inside back)
Screws,
typically 3
DIP
switches