Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Teamwork
Liebert
®
 iCOM
®
84
4.3.1 Tools Required for Installation
• Small, non-conductive tool for setting control DIP switches 
• Medium flat-head screw driver for opening electric panel protective dead-front.
• Cutting tool to trim cable ties
• Small Phillips-head screwdriver to open 2T housing
4.3.2 DIP Switch Settings
The individual 2T sensor must be given a unique address on the CANbus cable run to the associated 
Liebert unit. DIP switches are used to give the 2T sensor its unique address. It is important to 
confirm that the DIP switches have been set correctly using Table 17Although it is not required, it 
is recommended that the DIP switch sensor number settings correspond to the number of 2T sensors 
on the CANbus run. For example, if there are only four 2T sensors used for a particular Liebert CW 
unit then the individual DIP switch settings should correspond to address #1, #2, #3 and #4. If the 
DIP switches are not set correctly, the control will not operate properly.
Figure 70 DIP switches in 2T sensors
Table 17
DIP switch settings for remote sensor applications
2T Sensor #
DIP switch Position
1
2
3
4
5
6
7
8
1
Off
Off
On
Off
On
Off
Off
Off
2
On
Off
On
Off
On
Off
Off
Off
3
Off
On
On
Off
On
Off
Off
Off
4
On
On
On
Off
On
Off
Off
Off
5
Off
Off
Off
On
On
Off
Off
Off
6
On
Off
Off
On
On
Off
Off
Off
7
Off
On
Off
On
On
Off
Off
Off
8
On
On
Off
On
On
Off
Off
Off
9
Off
Off
On
On
On
Off
Off
Off
10
On
Off
On
On
On
Off
Off
Off
Switch Up = ON
Switch Down = OFF