Vulcan V SERIES 
 Owner’s Manual 
Canadian Comfort Industries                                    
                                                     
      E
XHAUST 
S
YSTEMS 
(
GENERAL
)
 
 
PELLET VENT MUST MAINTAIN A MINIMUM 3” CLEARANCE TO ANY COMBUSTIBLE  
(INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER). 
DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE 
OR STOVE. 
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT. 
PELLET VENT TYPE:  
Must be an approved 3” or 4” Diameter Type ”PL” vent, vented to the outside (fig. 7) or connect the vent to a 
factory built type “A” chimney using an adaptor; and/or “All Fuel” Stainless Steel  chimney liner for masonry 
fireplace installations (fig. 8) . Use 4” dia. vent if vent or liner height is over 15’ or if installation is over 4,000’ 
above sea level.  
 
VENTING DISTANCE: 
VENT INSTALLATION: 
Termination must exhaust above the air inlet elevation, and parallel or above the exhaust output of the 
pellet appliance.  It is recommended that at least 3’ of vertical pipe be installed to create some natural 
draft.  This is to help prevent the possibility of smoke or odor during the appliance shut down.  
 
Horizontal sections must have a ¼” rise every 12” of travel after 3’ long. 
Pellet Vent connections must be sealed with HI-Temp RTV Silicone and/or screwed together with at 
least 3 x 3/8” long stainless steel screws. Seal each vent section by injecting a liberal amount of HI-
TEMP RTV silicone sealant into the gap.