Vulcan V SERIES 
 Owner’s Manual 
Canadian Comfort Industries                                      
                                                     
Floor Pad
Floor
Frame
(bolts)
(ground wire)
M
OBILE 
H
OME 
I
NSTALLATION
 
 
CAUTION:   DO NOT INSTALL STOVE IN SLEEPING ROOM 
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, 
CEILING/ROOF MUST BE MAINTAINED! 
 
Your 
VULCAN “V” Series
 stove has been tested and listed for mobile home installation. It may be installed in a 
mobile home as a "Free Standing Stove" or a "Hearth Stove", see detailed install and clearance requirements 
in these sections as they imply there.   
 
In addition to all previously detailed installation requirements, mobile home installations 
must meet the following requirements: 
 
Permanently bolt your stove to the floor, (A), figure 26.   
 
Electrically ground your stove or the pedestal to the steel frame of the home. Use a number 8 gauge 
copper wire, (B), figure 26, or equivalent. 
 
The stove must have a permanent outside air source with a ¼ inch screen over the inlet.  
Figure 25, (B, C & D) 
 
 
For transportation all chimney/vent above the mobile home must be removed. 
 
Chimney/PL Vent must be 3” or 4” PL Vent and must extend a minimum or 36” above the roofline of 
the mobile home and must be installed using a UL / ULC listed ceiling fire stop (J), figure 25, and  
rain cap (L), figure 25.  
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER. 
Floor Pad 
Combustion Air Intake 
Fresh Air Duct 
Fresh Air Hood 
Stove Exhaust 
Pipe Adapter 
Clean Out Tee 
Tee Support Bracket 
Pipe 
Firestop Spacer / Ceiling Support 
Roof Flashing / Storm Collar 
Rain Cap  
 
 
 
 
 
 
 
   
 
 
 
 
                         Figure 25   
 
                   
Figure 26 
 
 
 
Note
: When moving your Mobile Home, all exterior venting must be removed while Mobile Home is 
being relocated. Upon completion of relocation all venting must be reinstalled and securely fastened.