TC12 Installation, Commissioning & Maintenance Handbook 
junction have been learnt in that state. If the learning of the second state is left to 
occur automatically at the next dim/bright change, and the lamp failure occurs 
during or just after the change, it will not be detected by the LMU until the 
controller reverts back to the original state in which the junction learning was 
invoked. 
 
3.3.4.4  Checking that Lamp Failures are Detected 
The installation engineer may check that lamp failures are indicated when they 
occur and that lamp replacements remove the fault indication. 
 
These checks should be carried out after the junction characteristics have been 
learnt. 
 
Remove any lamp and wait for the LMU to find the failure. Indication that the lamp 
failure has been found will be given by the lighting of the system fail LED on the 
OTU PCB, and by the appropriate entry in the fault log. The installation engineer 
may check that fault information produced by the LMU is recognised by the 
equipment (OTU or controller) to which the fault outputs are connected if required. 
 
Further lamps may be removed to check that lamp failures can be detected on 
other controller outputs. 
 