Class 8839 58M Enclosed AC Drives
Specifications
177
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
d. There shall be no restriction on space 
requirements between floor mounted 
enclosures
e. A mechanical interlock shall prevent 
personnel from opening the AC Drive door 
when the disconnect is in the “ON” position. It 
shall be possible for authorized personnel to 
defeat this interlock. Provisions shall be 
provided for locking all disconnects in the off 
position with up to three padlocks. Provisions 
shall also be made for accepting a padlock on 
the circuit breaker disconnect, preventing 
movement of the disconnect to the “ON” 
position when the door is open. 
f.
Provisions shall be made for both top and 
bottom conduit entry. Conduit knockouts shall 
be provided for wall mounted enclosures. 
Removable conduit entry plates shall be 
provided for floor mounted enclosures.   
g. All fans within an enclosed AC Drive including 
the AC Drive heatsink fans shall be front 
accessible and removable without removal of 
the AC Drive power converter to facilitate 
maintenance and or fan replacement. 
h. Control wiring shall have permanent wire 
markings printed on the wire insulation. Both 
ends of the control wiring shall contain wire 
markings per the as built control elementary 
diagram. Red control wiring shall be used for 
115Vac control circuits and blue control wiring 
shall be used for 24V control circuits.
i.
All AC Drive enclosure shall be painted ANSI 
49 Gray. The enclosure interior shall include a 
white mounting surface for control and power 
component mounting for improved visibility. 
2.04 MOTOR DATA
a. The AC Drive shall be sized to operate the 
following AC motor:
Motor Horsepower 
[1,2,3,5,7.5,10,15,20,25,30,40,50,60,75,100,
125,150,200,250,300,350,400,450,500]
Motor full load ampere [specify rating 
coordinated to NEC Table 430-150]
Motor RPM [3600/3000,1800/1500,
1200/1000,900/750,720/600,600/500]
 at 
60 Hz
Motor voltage [208,230,460]
Motor service factor [1.0,1.15,1.25]
2.05 APPLICATION DATA
a. The AC Drive shall be sized to operate a 
[Variable Torque, Constant Torque] load.
b. The speed range shall be from a minimum 
speed of 0.5 Hz to a maximum speed of 
400 Hz.
2.06 ENVIRONMENTAL RATINGS
a. The AC Drive shall be of construction that 
allows operation in a pollution Degree 3 
environment. The AC Drive shall meet IEC 
60664-1 and NEMA ICS 1 Standards. AC 
Drives that are only rated for Pollution Degree 
2 environment shall not be allowed.
b. The AC Drive shall be designed to operate in 
an ambient temperature from 0 to + 40 °C 
(+32 to 104 °F).
c. The storage temperature range shall be -25 to 
+ 70 °C (-13 to 158 °F).
d. The maximum relative humidity shall be 95% 
at 40 °C (104 °F), non-condensing.
e. The AC Drive shall be rated to operate at 
altitudes less than or equal to 3,300 ft 
(1000 m). For altitudes above 3,300 ft, de-rate 
the AC Drive by 1% for every 300 ft (100 m).
f.
The AC Drive shall meet the IEC 60068-2 
Operational Vibration Specification.
2.07 RATINGS
a. The AC Drive shall be designed to operate 
from an input voltage of 460 
±
 10% Vac or 
208 -15% to 230 +15% Vac.
b. The AC Drive shall operate from an input 
voltage frequency range of 60 Hz 
±
 2%.
c. The displacement power factor shall not be 
less than .95 lagging under any speed or load 
condition.
d. The efficiency of the AC Drive at 100% speed 
and load shall not be less than 96%.
e. The [constant, variable] torque rated AC Drive 
overcurrent capacity shall be [150%, 110%] 
for one minute.
f.
The output carrier frequency of the AC Drive 
shall be randomly modulated and selectable 
at 2, 4, or 10 kHz depending on Drive rating for 
low noise operation. No AC Drive with an 
operable carrier frequency above 10 kHz shall 
be allowed.
g. The output frequency shall be from 0.1 to 
400 Hz for AC Drives up to 75 hp. For 
horsepower ratings above 75 hp, the 
maximum output frequency will be 200 Hz.