Schneider Electric ALTIVAR 58 TRX Manual De Usuario

Descargar
Página de 232
Altivar
®
 
58 TRX AC Drives
Communication Parameters
83
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
W262
or 16#5FE5/D
JOG
0.1 Hz
Jog frequency
0 to 100 (0.0 to 10.0 Hz)
W263
or 16#5FE5/E
JGT
0.1 s
Delay between two consecutive jog operations
0 to 20 (0.0 to 2.0 s)
W264
or 16#5FE5/F
SP2
0.1 Hz
Preset speed 2
LSP to HSP
W265
or 16#5FE5/10
SP3
0.1 Hz
Preset speed 3
LSP to HSP
W266
or 16#5FE5/11
SP4
0.1 Hz
Preset speed 4
LSP to HSP
W267
or 16#5FE5/12
SP5
0.1 Hz
Preset speed 5
LSP to HSP
W268
or 16#5FE5/13
SP6
0.1 Hz
Preset speed 6
LSP to HSP
W269
or 16#5FE5/14
SP7
0.1 Hz
Preset speed 7
LSP to HSP
W270
or
16#5FE5/15
IDC
0.1 A
DC injection current level
0.1 to 1.36
x INV (drive controller nominal current)
W271
or 16#5FE5/16
TDC
0.1 s
DC injection time (in the case of automatic DC 
injection at stop)
Type FVC: Zero speed holding time with CTR = 
closed loop
0 to 300 = 0.0 s to 30.0 s
301 = CONT: continuous injection
W272
or 16#5FE5/17
TLS
0.1 s
Low speed (LSP) dwell timer
0 = No: no limit
1 to 9999 = time of 0.1 s to 999.9 s
W273 
[1]
or 16#5FE5/18
BRL
0.1 Hz
Mechanical brake release threshold
0 to 100 (0.0 to 10.0 Hz)
W274
or 16#5FE5/19
BEN
0.1 Hz
Mechanical brake engage threshold 
Type FVC: Not significant if 
CTR = closed loop
0 to LSP
W275
or 16#5FE5/1A
BRT
0.01 s
Mechanical brake release time
0 to 500 (0.00 to 5.00 s)
W276
or 16#5FE5/1B
BET
0.01 s
Mechanical brake engage time
0 to 500 (0.00 to 5.00 s)
W277
or 16#5FE5/1C
IBR
0.1 A
Mechanical brake release current threshold
0 to 1.36
x INV (drive controller nominal current)
W278
or 16#5FE5/1D
TL2
1%
Second torque limit
0 to 200
W279
or 16#5FE5/1E
RPG
0.01
PI proportional gain
1 to 10000 (0.01 to 100.00)
W280
or 16#5FE5/1F
RIG
0.01/s
PI integral gain
1 to 10000 (0.01 to 100.00)
W281 
[1]
or 16#5FE5/20
FBS
0.1
PI feedback scale factor
10 to 1000 (1.0 to 100.0)
W282
or 16#5FE5/21
CTD
0.1 A
Motor current threshold for signalling
0.25 to 1.36 x INV
(INV = drive controller nominal current)
W283
or 16#5FE5/22
TTD
1%
Thermal threshold for signalling
0 to 118
W284
or 16#5FE5/23
FTD
0.1 Hz
Frequency threshold for signalling
LSP to HSP
W285
or 16#5FE5/24
DTS
0.01
Tachogenerator feedback scaling (For I/O card 
with analog input)
100 to 200 (1.00 to 2.00)
W286
or 16#5FE5/25
JPF
0.1 Hz
Skip frequency
(frequency range: ±2.5 Hz)
0 to HSP
W287
or 16#5FE5/26
PIC
Inverts the PI feedback signal
0 = No (normal)
1 = Yes (inverted)
W288
16#5FE5/27
SDC
0.1 A
Continuous DC injection braking current level on 
stopping after 30 s. See TDC (W271)
Min: 0.1 x INV
Max: 1.36 x INV
(INV = drive controller nominal current)
W289
or 16#5FE5/28
USC
0.01
Machine coefficient. Applied to RFR for custom 
display of machine speed under Display parameter 
USP (USP = RFR x USC).
1 to 10000 (0.01 to 100.00)
W290
or 16#5FE5/29
BIP
Brake release pulse
0 = No: Pulse in the direction requested
1 = Yes: Always pulse in the ascending direction 
W291
or 16#5FE5/2A
INR
Fine increment in the ramp settings for ACC, DEC, 
AC2, and DE2
0 = 0.1 s
1 = 0.01 s
W292
or 16#5FE5/2B
SRP
1%
Range of action around the reference for +/– 
speed function
0 to 50% of the reference 
W293
or 16#5FE5/2C
TA1
1%
Rounding of the start of the acceleration ramp
0 to 100% of ramp time
Adjustment Registers (Continued)
Word
Code
Units
Description
Possible Values or Range
[1]
This parameter does not exist for ATV58 Type FVC drive controllers.