Communication Parameters
©
 2000–2003 Schneider Electric All Rights Reserved
84
09/2003
W294
or 16#5FE5/2D
TA2
1%
Rounding of the end of the acceleration ramp
0 to (100% of ramp time – TA1)
W295
or 16#5FE5/2E
TA3
1%
Rounding of the start of the deceleration ramp
0 to 100% of ramp time
W296
or 16#5FE5/2F
TA4
1%
Rounding of the end of the deceleration ramp
0 to (100% of ramp time – TA3)
W297
or 16#5FE5/30
SPG
1%
PI type speed loop proportional gain 
0 to 1000
W298
or 16#5FE5/31
SIG
1%
PI type speed loop integral gain 
0 to 1000
W299
or 16#5FE5/32
REO
PID regulator reference offset
–999 to +999
W300
or 16#5FE5/33
PAL
1%
PID feedback alarm min. threshold
0 to 100%
W301
or 16#5FE5/34
PAH
1%
PID feedback alarm max. threshold
0 to 100%
W302
or 16#5FE5/35
PER
1%
PID error alarm max. threshold
0 to 100%
W303
or 16#5FE5/36
RDG
0.01
PID regulator derivative gain
0 to 10000 (0 to 100.00)
W304
or 16#5FE5/37
PSP
0.1 s
PID feedback filter time constant
0 to 100 (0 to 10.0)
W305
or 16#5FE5/38
PSR
1%
PID speed input multiplier ratio
0 to 100
W306
or 16#5FE5/39
PLR
1%
PID regulator deadband ratio
0 to 100
W307
or 16#5FE5/3A
PLB
0.1 Hz
PID regulator deadband threshold
0 to HSP
W308
or 16#5FE5/3B
PI2
1%
2nd preset PID reference 
0 to 100
W309
or 16#5FE5/3C
PI3
1%
3rd preset PID reference 
0 to 100
W310
or 16#5FE5/3D
PRG
PID regulator reference gain
–999 to +999
W311
or 16#5FE5/3E
JF2
0.1 Hz
Skip frequency 2
± 2.5 Hz around setpoint
0 to HSP
W312
or 16#5FE5/3F
JF3
0.1 Hz
Skip frequency 3
± 2.5 Hz around setpoint
0 to HSP
W313
or 16#5FE5/40
FFT
0.1 Hz
Frequency threshold for start of freewheel stop 
during deceleration phase if STT (W79) = STN or 
FST
0 to HSP
W314
or 16#5FE5/41
F2D
0.1 Hz
Second frequency threshold for signalling
LSP to HSP
W315
or 16#5FE5/42
DTD
1%
Drive thermal state threshold value
0–118%
W316
or 16#5FE5/43
SP8
0.1 Hz
Preset speed 8 (125–500 hp only)
LSP to HSP
W317
or 16#5FE5/44
NAR
1
Number of restart attempts
0–255
W318
or 16#5FE5/45
TAR
s
Time between auto restarts
0.1–999.9
Adjustment Registers (Continued)
Word
Code
Units
Description
Possible Values or Range
[1]