Royal Appliance Air Furnace Manual De Usuario

Descargar
Página de 40
 
29733 R2  06/01/2003
 
11
The furnaces may be installed with a one-pipe system 
with gravity feed or lift. The maximum allowable lift on a 
single line system is 8 feet. Lift should be measured from 
the bottom (outlet) of the tank, to the inlet of the burner. 
Sizing a single line system is complex because of the 
difficulty estimating the pressure drop through each 
fitting, bend and component in the line. In general, keep 
single line systems short as possible. If the furnace is to 
be installed in a suspended position, a two-pipe system 
may be the better alternative. 2-stage oil pumps are not 
available for either the Beckett or Riello burner. The 
following chart shows the allowable line lengths 
(horizontal + vertical) for single and two stage oil pumps. 
All distances are in feet. 
 
In retrofit applications, where an existing oil line system is 
in place, a vacuum check will help determine the efficacy 
of the existing oil line system The vacuum in a system 
featuring a Beckett burner should not exceed 6” Hg. for a 
single pipe system, nor 12” Hg. for a two-pipe system. 
The vacuum in a system featuring a Riello burner should 
not exceed 6” Hg. for a single pipe system, nor 11.44” 
Hg. for a two-pipe system. 
 
Table 5: Oil Lines 
Copper Tubing Oil Line Lengths (Feet) 
Beckett Oil Burner 
Single-Pipe Two-Pipe 
Lift 
(feet) 
⅜” O.D. 
Tubing 
½” O.D. 
Tubing 
⅜” O.D. 
Tubing 
½” O.D. 
Tubing 
0 53 100 68 100 
1 49 100 65 100 
2 45 100 63 100 
3 41 100 60 100 
4 37 100 58 100 
5 33 100 55 100 
6 29 100 53 100 
7 25 99 50 100 
8 21 83 48 100 
9 17 68 45 100 
10 13 52  42  100 
12 
- - - 
- - - 
37 
100 
14 
- - - 
- - - 
32 
100 
16 
- - - 
- - - 
27 
100 
18 
- - - 
- - - 
22 
88 
 
Riello Oil Burners 
Single-Pipe Two-Pipe 
Lift 
(feet) 
⅜” O.D. 
Tubing 
½” O.D. 
Tubing 
⅜” O.D. 
Tubing 
½” O.D. 
Tubing 
1.5 33  65 100 330 
3.0 65 130 80  330 
5.0 130 260  65  295 
6.5 195 325  50  230 
9.5 
- - - 
- - - 
25 
100 
11 
- - - 
- - - 
20 
65 
 
For additional information, see the installation information 
sheet included in the documents envelope or affixed to 
the oil burner. 
 
NOTE: Both the Beckett and Riello oil burners require the 
use of a bypass plug when converting from single-pipe to 
two-pipe oil piping systems. See burner manufacturer’s 
instructions. 
 
NOTE: The Riello oil burner is manufactured with British 
Parallel Thread pump ports. Adapters are supplied with 
the oil burner to convert from British Parallel Thread to 
NPT (National Pipe Thread). Direct connection of NPT 
fittings to the Riello oil burner ports will result in damage 
to the pump body. This also applies to pressure and 
vacuum gauges. (See Riello manual) 
 
13.  OIL FILTER 
All fuel systems should include an oil filter between the 
fuel oil storage tank and the oil burner. For best results, 
install the oil filter as close to the burner as possible. 
When using an indoor oil tank, the oil filter may be 
installed at the tank downstream from the shut-off valve. 
If firing the furnace under the 0.65 gph rate, a 7 to 10 
micron line filter should be installed as close to the oil 
burner as possible.  
 
14.  OIL BURNER NOZZLES 
The 80F Series furnace is certified for multiple firing 
rates, ranging from 58,100 to 78,900 BTU/hr, while the 
120F Series Furnace is certified for multiple firing rates of 
87,000 113,400 BTU/hr. By changing the oil burner 
nozzle within the specific Model Range, and temperature 
rise, the furnace may be fired at an ideal rate for a wide 
range of structures.  
 
Table 6: Nozzles (Beckett Oil Burner) 
NOZZLE (Delavan) 
HEAD 
MODEL 
STD. ALT.  
80F (060) 
0.50/70°W 
0.50/80°A 
F0 
80F (070) 
0.65/70°W 
0.65/80°A 
F3 
80F (080) 
0.70/70°W 
0.70/80°A 
F3 
120F (090) 
0.75/70°W 
0.75/80°A 
F4 
120F (100) 
0.80/70°W 
0.80/80°A 
F4 
120F (120) 
1.00/70°W 
1.00/80°A 
F4 
 
15. COMBUSTION CHAMBER 
This furnace is equipped with an efficient cerafelt 
combustion chamber. It is held in place by a retaining 
bracket.