Royal Appliance Air Furnace Manual De Usuario

Descargar
Página de 40
 
29733 R2  06/01/2003
 
9
installed in accordance to the instructions supplied with 
the regulator. 
 
8.  FURNACE CONTROLS 
The furnace is controlled by either of two systems, 
depending on the oil primary control and electronic fan 
timer combination. System 1, used with Beckett burners, 
includes the blower mounted Honeywell ST9103 
E
LECTRONIC 
F
AN 
T
IMER 
(EFT) combined with the R7184 
O
IL 
P
RIMARY 
C
ONTROL
. System 2, used with Riello 
burners, includes the blower mounted Honeywell ST9103 
E
LECTRONIC 
F
AN 
T
IMER 
(EFT) combined with a 
transformer / burner relay mounted internally on the 40F3 
burner housing to operate the oil burner.  
Figure 3: R7184 Oil Primary 
 
The furnace functions are controlled by either System 1 
or System 2, and bi-metallic snap disc limit switches. 
These groupings also provide control for add-on air 
conditioning. The ST9103 EFT is located in a control box 
mounted to the blower support rails.  
 
The circulating fan is controlled by the ST9103 EFT. The 
heat delay-on time is fixed, at 30 seconds. This provides 
a delay between the start of the burner and the start of 
the circulating fan to reduce the amount of ambient 
unheated air flowing through the ductwork. The end of 
the circulating fan cycle is also delayed to remove 
residual heat from the furnace. There are four delay-off 
choices, 60, 90, 120 and 150 seconds, which are field 
adjustable by manipulating the DIP switches on the 
ST9103 EFT board. 
 
The cooling delay-on and delay-off times are fixed at 30 
seconds. 
 
The furnace is protected against over-heating by fixed 
high temperature limits. These controls are factory set 
and are not field adjustable. If an over temperature 
condition is detected, one or both limit switches will 
interrupt power to the oil primary control, which will shut 
of the oil burner. The circulating fan will continue to 
operate. The high limit switches will automatically reset 
when the furnace returns to a safe temperature. 
 
 
9.  ELECTRICAL CONNECTIONS 
The furnace is listed by the Canadian Standards  
Association  (CSA). It is factory wired and requires 
minimal field wiring. In the United States, the wiring must 
be in accordance with the National Fire Protection 
Association NFPA-70
,  National Electrical Code, and 
with local codes and regulations. In Canada, all field 
wiring should conform to CAN/CSA C22.1  Canadian 
Electrical Code, Part 1
, and by local codes, where they 
prevail.  
 
The furnace should be wired to a separate and dedicated 
circuit in the main electrical panel; however, accessory 
equipment such as electronic air cleaners and humidifiers 
may be included on the furnace circuit. Although a 
suitably located circuit breaker can be used as a service 
switch, a separate service switch is advisable. The 
service switch is necessary if reaching the circuit breaker 
involves becoming close to the furnace, or if the furnace 
is located between the circuit breaker and the means of 
entry to the furnace room. The furnace switch (service 
switch) should be clearly marked, installed in an easily 
accessible area between the furnace and furnace room 
entry, and be located in such a manner to reduce the 
likelihood that it would be mistaken as a light switch or 
similar device. 
Figure 4: ST9103 EFT