F-2200 Series Vortex Flow Meter Installation and Operation Guide • Revised 12/08
17 
 3.3.2 
Temperature 
Measurements
 
 
ONICON F-2000 series vortex meters are supplied with an internal PT 1000 type RTD 
 
 
temperature sensor located within the shedder bar. This sensor provides an accurate 
 
 
temperature measurement at the point where the fl ow rate is being measured. Flow meters 
 
 
supplied with this option will display the medium temperature and deliver an output signal 
 
 
that is temperature compensated for mass and/or normalized fl ow. 
3.3 WIRING 
TERMINATIONS
 
The standard F-2000 series vortex meter is a 2-wire loop powered device. Wiring  connections are shown 
 below.
CAUTION
• 
Do not remove enclosure covers in any wet environment 
• 
Keep dirt and debris out of electronics enclosure 
• 
Keep threads lubricated (silicone based lubricant) 
• 
Do not over tighten covers. Use special tool for removal only.
4-20 mA
100 ohms 
minimum