Toshiba 18 - 1250 A Manual De Usuario

Descargar
Página de 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
80 
 
Fn# 
Function 
Type 
Setting 
Function Description / Range 
Timer 
Initiated 
By… 
Motor 
Starts 
When… 
Motor 
Stops 
When… 
Timer 
Reset  
When… 
F030 
Process 
Control 
Timer 
Mode 
No Process Control Timer operation (default setting from factory) 
Minimum (Batch) Run Timer  
(works the same with or without TCC 
control) 
Start 
command 
and/or 
TCC 
Start 
command  
Time 
Expires, 
Trip, or 
Stop 
Command 
Time 
Expires + 
Stop 
command 
only 
Permissive Run Timer, without TCC  
(F032 =0, “One Shot”) 
Start 
command 
Start 
command  
Time 
Expires 
Permissive Run Timer, with TCC  
(F032 = 2 thru 8) 
TCC Start 
Event 
only 
Next SEC 
only 
F031 
Process 
Timer 
Value 
Run 
Time 
Value 
Timer value setting used by F030 
Range: 1 – 9999 minutes (166.65 
hours) 
--- --- 
Per F030 
setting 
F032 
24 hr /  
7 day 
  
Time Clock 
Controller 
One-Shot, follows Start command only 
Start 
command 
Start 
command 
Per F030 
setting 
Per F030 
setting 
Loop the Start Even Cycle (SEC) daily 
24hr Real 
Time 
Clock on 
day of 
program 
change  
Per F030 
setting 
Per F030 
setting 
Continuous 
unless 
program is 
changed 
Loop the 24hr SEC every other day 
Loop the 24hr SEC every 3
rd
 day 
Loop the 24hr SEC every 4
th
 day 
Loop the 24hr SEC every 5
th
 day 
Loop the 24hr SEC every 6
th
 day 
Loop the 24hr SEC one day per week 
Single 24hr SEC, without repeating  
(until programmed again) 
Change of 
Program  
F033 Event 
#1 
Start 
time 
24hr TCC Start Time for Event #1 
F032 =1-8
Continuous 
unless 
program is 
changed 
F034 Event 
#2 
Start 
time 
24hr TCC Start Time for Event #2 
F035 Event 
#3 
Start 
time 
24hr TCC Start Time for Event #3 
F036 Event 
#4 
Start 
time 
24hr TCC Start Time for Event #4 
F037 Event 
#5 
Start 
time 
24hr TCC Start Time for Event #5 
F038 Event 
#6 
Start 
time 
24hr TCC Start Time for Event #6 
F039 Event 
#7 
Start 
time 
24hr TCC Start Time for Event #7 
Chart APP 4.1 
Process Timer and TCC Operations Logic Chart 
 
 
ƒ 
NOTE:  
These functions may interact with the Coast Down Lockout (F048), 
Stars-per-Hour Lockout (F049), Minimum Time Between Starts 
(F050), Auto-Reset (F052) and Restart Delay Time (F028) functions 
if enabled. Be sure to read and understand descriptions of those 
functions, then check settings before using the Process Control 
Timer.