Toshiba 18 - 1250 A 사용자 설명서
TE Series
Digital Solid State Soft Starters 18 – 1250A
80
Fn#
Function
Type
Setting
Function Description / Range
Timer
Initiated
By…
Motor
Starts
Starts
When…
Motor
Stops
Stops
When…
Timer
Reset
Reset
When…
F030
Process
Control
Timer
Mode
0
No Process Control Timer operation (default setting from factory)
1
Minimum (Batch) Run Timer
(works the same with or without TCC
control)
(works the same with or without TCC
control)
Start
command
and/or
TCC
Start
command
Time
Expires,
Trip, or
Stop
Command
Time
Expires +
Stop
command
only
2
Permissive Run Timer, without TCC
(F032 =0, “One Shot”)
(F032 =0, “One Shot”)
Start
command
Start
command
Time
Expires
Permissive Run Timer, with TCC
(F032 = 2 thru 8)
(F032 = 2 thru 8)
TCC Start
Event
only
Next SEC
only
F031
Process
Timer
Value
Value
Run
Time
Value
Timer value setting used by F030
Range: 1 – 9999 minutes (166.65
hours)
Range: 1 – 9999 minutes (166.65
hours)
--- ---
Per F030
setting
F032
24 hr /
7 day
Time Clock
Controller
7 day
Time Clock
Controller
0
One-Shot, follows Start command only
Start
command
Start
command
Per F030
setting
Per F030
setting
1
Loop the Start Even Cycle (SEC) daily
24hr Real
Time
Clock on
day of
program
change
Per F030
setting
Per F030
setting
Continuous
unless
program is
changed
2
Loop the 24hr SEC every other day
3
Loop the 24hr SEC every 3
rd
day
4
Loop the 24hr SEC every 4
th
day
5
Loop the 24hr SEC every 5
th
day
6
Loop the 24hr SEC every 6
th
day
7
Loop the 24hr SEC one day per week
8
Single 24hr SEC, without repeating
(until programmed again)
(until programmed again)
Change of
Program
F033 Event
#1
Start
time
24hr TCC Start Time for Event #1
F032 =1-8
Continuous
unless
program is
changed
F034 Event
#2
Start
time
24hr TCC Start Time for Event #2
F035 Event
#3
Start
time
24hr TCC Start Time for Event #3
F036 Event
#4
Start
time
24hr TCC Start Time for Event #4
F037 Event
#5
Start
time
24hr TCC Start Time for Event #5
F038 Event
#6
Start
time
24hr TCC Start Time for Event #6
F039 Event
#7
Start
time
24hr TCC Start Time for Event #7
Chart APP 4.1
Process Timer and TCC Operations Logic Chart
NOTE:
These functions may interact with the Coast Down Lockout (F048),
Stars-per-Hour Lockout (F049), Minimum Time Between Starts
(F050), Auto-Reset (F052) and Restart Delay Time (F028) functions
if enabled. Be sure to read and understand descriptions of those
functions, then check settings before using the Process Control
Timer.
These functions may interact with the Coast Down Lockout (F048),
Stars-per-Hour Lockout (F049), Minimum Time Between Starts
(F050), Auto-Reset (F052) and Restart Delay Time (F028) functions
if enabled. Be sure to read and understand descriptions of those
functions, then check settings before using the Process Control
Timer.