Toshiba TOSVERT VF-S11 Manual De Instrucciónes

Descargar
Página de 81
E6581160
10
2
2. Connection
2.1
Standard connections
2.1.1     Standard connection diagram 1
This diagram shows a standard wiring of the main circuit.
MCCB
*1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
I M
FLC
FLB
FLA
RY
RC
PLC
Motor
F
R
RES
S1
S2
S3
CC
P24
OUT
NO
CC
FM
PLC
CC VIA
VIB
PP
+
+
-
-
P0
PA/+
PB
PC/-
Meter
Voltage signal: 0-10V 
(Current signal: 4-20mA)
External potentiometer (1~10k
Ω)
(or input voltage signal across VIB-CC terminals: 0-10V)
Control 
circuit
Operation panel
Protective function 
activation output
Ry
VF-S11
Frequency 
meter
 (ammeter)
Power circuit
Noise 
filter
DC reactor (DCL) 
*2 (option)
Connector for 
common serial 
communications
Forward
Reverse
Reset
Preset-speed 1
Preset-speed 2
Preset-speed 3
Common
Braking resistor (option)
Standard connection diagram - SINK (Negative) (common:CC)
Low-speed 
signal output
24Vdc input
7.5V-1mA
(or 4-20mA)
MCCB(2P)
R/L1
S/L2
Power supply
1   200~240V
-50/60Hz
Speed reach 
signal output
I
I
SINK
SW1 
SOURCE
FM 
V
VIA 
V
Main circuit power supply
240V class: three-phase 200-240V
                    -50/60Hz
500V class: three-phase 380-500V
                    -50/60Hz
600V class: three-phase 525-600V
                    -50/60Hz
*1: The T/L3 terminal is not provided
      for single-phase models.
     Use the R/L1 and S/L2 terminal 
      as input terminals.
*2: The inverter is supplied with the PO 
     and the PA/+ terminals shorted by
     means of a shorting bar.
     Before installing the DC reactor (DCL), 
     remove the bar.
*3: When using the OUT output terminal in 
     sink logic mode, short the NO and CC
     terminals.
*4: If you are using a 600V model, be sure 
     to connect an input reactor (ACL). 
*5: 600V models have no noise filter inside. 
*3
*5