2
2.1.2     Standard connection diagram 2
MCCB
*1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
I M
FLC
FLB
FLA
RY
RC
PLC
Motor
P24
F
R
RES
S1
S2
S3
P24
OUT
NO
CC
+
+
-
-
P0
Meter
External potentiometer (1~10k
Ω)
(or input voltage signal across VIB-CC terminals: 0-10V)
Control 
circuit
Operation panel
Protective function 
activation output
VF-S11
Frequency 
meter 
(ammeter)
Power circuit
Noise 
filter
*1: The T/L3 terminal is not provided 
     for single-phase models.
    Use the R/L1 and S/L2 terminal 
     as input terminals.
*2: The inverter in supplied with the PO 
       and the PA/+ terminals shorted by 
       means of a shorting bar. 
       Before installing the DC reactor (DCL), 
       remove the bar.
*3: When using the NO output terminal in 
     source logic mode, short the P24 and 
     OUT terminals. 
*4: If you are using a 600V model, be sure 
     to connect an input reactor (ACL).
*5: 600V models have no noise filter inside. 
DC reactor (DCL) 
*2 (option)
Connector for 
common serial 
communications
Forward
Reverse
Reset
Preset-speed 1
Preset-speed 2
Preset-speed 3
Braking resistor (option)
Standard connection diagram - SOURCE (Positive) (common:P24)
Low-speed
signal output
24Vdc input
7.5V-1mA
(or 4-20mA)
MCCB(2P)
R/L1
S/L2
Main circuit power supply
240V class: three-phase 200-240V
                    -50/60Hz
500V class: three-phase 380-500V
                    -50/60Hz
600V class: three-phase 525-600V
                    -50/60Hz
Power supply
1    200
~
240V
-50/60Hz
FM
CC VIA VIB
PP
PLC
PA/+
PB
PC/-
Voltage signal: 0-10V 
(Current signal: 4-20mA)
I
I
SINK
SW1 
SOURCE
FM 
V
VIA 
V
*5
Speed reach signal 
output
*3
Ry