HP Performance Optimized Data Center (POD) 240a Manual De Usuario
Environmental control system 46
The AD detail screen displays the following minimum and maximum alarm setpoint ranges that you can
configure:
Setpoint displayed
Description
HA return temperature
Indicates the temperature reading from the hot
aisle
HA static pressure
Indicates the pressure value reading from the hot
aisle in relation to the external ambient
temperature
CA wall temperature
Indicates the temperature from the wall sensor
located in the IT sections
located in the IT sections
CA temperature combo
Indicates the average temperature from the wall
sensor and discharge temperature sensor
CA relative humidity
Indicates the relative humidity percentage from the
wall sensor
wall sensor
CA dew point
Indicates the dew point temperature from the wall
sensor
CA static pressure
Indicates the pressure value reading from the IT
sections in relation to the external ambient
pressure
pressure
CA discharge temperature Indicates the discharge air temperature
The AD detail screen displays the following operational parameters for each AHU: