Life safety systems  18 
Life safety systems 
Life safety overview 
The HP POD 20c has multiple life safety systems that work together to protect the HP POD 20c equipment and 
personnel. The following life safety systems are available on the HP POD 20c: 
 
EPO system (on page 
) 
 
VESDA air sampling smoke detection system (on page 
) 
 
(Optional) fire protection system (on page 
) 
 
Emergency egress (on page 
) 
 
ECS connection to customer emergency systems 
 
EPO system 
If the HP POD 20c must be shut down during an emergency, the EPO system automatically shuts off all power 
to the HP POD 20c and activates the EPO indicator on the ECS panel door and the EPO strobe on the POD 
interior. 
To ensure that all rack-mounted UPS devices are shut down during an EPO event, verify that each 
rack-mounted UPS device is connected to the HP POD 20c EPO system. 
The EPO system can be activated two ways: 
 
Excessive high temperature in the hot aisle—The HP POD 20c includes two EPO temperature sensors. 
If both sensors reach 60°C (140°F), an EPO shutdown is triggered automatically. Both sensors are 
located in zone 2. 
 
 
Manual initiation—To manually trigger an EPO shutdown, press either of the EPO buttons. One EPO 
button is located on the POD interior near the main exit, and an optional second EPO button is located 
on the POD exterior.