HP Performance Optimized Data Center (POD) 20cp Manual De Usuario

Descargar
Página de 86
 
Life safety systems  20 
Item  Component 
Indicator Color 
Description 
EPO mode key control 
— 
Enables you to select the EPO mode. For 
more information, see "EPO modes (on 
page 
)." 
EPO shutdown button 
Red 
Initiates a manual EPO event 
10 
Light test button 
— 
Tests all the EPO LED indicators when 
pressed 
11 
EPO bypass mode indicator 
Green 
Indicates that the EPO shut down 
functionality is bypassed 
12 
EPO test mode indicator 
Yellow 
Indicates that the EPO system is operating 
in test mode or that an EPO cover is open 
13 
Main light switch 
— 
Turns power to the HP POD 20c lights off 
and on 
14 
ECS power switch 
— 
Turns the main power to the 24V ECS 
system off and on 
 
 
EPO modes 
The EPO system has three operating modes: 
 
Armed—The EPO system is armed and operational. 
 
Test—The EPO system is in test mode and does not initiate during events that normally trigger an EPO. 
 
Bypass—The EPO system is non-operational and does not initiate during events that normally trigger an 
EPO. 
 
EPO accidental activation 
To help prevent accidentally pressing the EPO button and activating the EPO system, each EPO button is 
covered with a clear Lexan cover. 
 
Battery backup during an EPO event 
The following components are equipped with a UPS to help ensure that service is not interrupted during a loss 
of power to the HP POD 20c: 
 
ECS system 
 
VESDA air sampling smoke detection system (on page 
) 
 
(Optional) fire suppression system (on page 
) 
 
Emergency lighting in the HP POD 20c 
  
 
IMPORTANT:
  All Critical IT UPS devices with batteries that exceed 700VA must be connected to 
the HP POD 20c EPO system, to ensure that the UPS batteries are disconnected during an EPO 
event. For more information on connecting UPS devices to the EPO system, see the HP 
Performance Optimized Datacenter 20c Maintenance and Service Guide.