Galaxy 3 Series Installation Manual
A-5
Keypad Group Restriction: To restrict the operation of the function only to groups that are
common to both the card and the MAX, press the   key when assigning groups to the MAX.
This means that when a card with access to groups 1, 2 and 3 activates the MAX card function
on a MAX module assigned to groups 2, 3 and 4, the function only operates on the common
groups (groups 2 and 3).
6.
Exit engineer mode — engineer code + esc: the keypad displays the message 
1 MOD. ADDED 
esc=CONTINUE
. LED 2 on the MAX reader switches on. Press the esc key; the keypad returns to the
unset banner.
If this message is not displayed, the MAX reader is not communicating with the control panel and has not
been configured into the system (LED 2 does not switch on).
NOTES:
1. The MAX reader will not operate until engineer mode is exited and the reader is configured into the
system.
2. All MAX doors must be closed, otherwise engineer mode cannot be exited.
7.
The on-line MAX reader is now configured into the system
Removing a MAX Reader from the System
Stand Alone Mode
The stand-alone MAX reader is not connected to the AB line, therefore it can be removed simply by
disconnecting the power to the reader. There is no requirement to access engineer mode.
On-Line Mode
1.
Access engineer mode.
2.
Disconnect the MAX reader (AB line and power).
3.
Exit engineer mode.
The message 
1 MOD. MISSING  [<],[>] to View
 is displayed.
4.
Press the A or B key.
The message 
MAX X   =REMOVE MODULE 
is displayed.
5.
Press the 
key to acknowledge and accept that the MAX reader has been removed. The keypad
returns to the unset banner.
Programming Instructions for On-Line Readers
Refer to Section 6: System Operation, menu option 63 = OPTIONS  for details on programming the
Open TimeoutClose Timeout and Group parameters for the MAX reader.
NOTE: These programming instructions refer only to on-line MAX readers (modules that are
connected to a host Galaxy panel via the RS485 data bus). For details on stand-alone MAX
installation refer to the MAX Installation and Operations Guide (L120).
For details on the programming of the MAX user cards and functions refer to Section 6: System
Operation
, menu option 42 = CODES.
Removing MAX Readers