Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 84
Operation
22
The Value setting is the factory default setting on free-cooling and dual cooling units. If the tempera-
ture difference between the second source cooling fluid parameter, Free-cooling Fluid Temperature 
(User Menu, Sensor Data) and room air is equal to or greater than the adjustable DT Between Room 
Air / FC Fluid (Service Menu, Setpoints) value, then the second source cooling fluid will be used to 
provide at least partial cooling (delta T between room and glycol = true).
Sensors used for this delta T are: room/local sensor or the return air sensor; and the glycol sensor.
If this delta T is true, the following actions will be performed:
1. The Free-Cooling Status indication will show “On” instead of “Off”.
2. The compressor band will be shifted to the right by 100%, and within the first 100% the free-
cooling valve band will take place (see Figure 18).
Figure 18 Second cooling source and compressorized cooling
Minimum Chilled Water Temperature—This feature permits the user to select the minimum 
chilled water temperature that allows simultaneous operation of the second cooling source (chilled 
water control) and compressor control. This feature is enabled in the Service menu under Setpoints, 
parameter Minimum CW Temp.
Below this minimum chilled water setpoint, parameter Minimum CW Temp Value, (Service Menu, 
Setpoints), the control will operate ONLY the second cooling source control, i.e., the compressor is 
locked out. Above the minimum chilled water setpoint, assuming the fluid temperature is below the 
return room air temperature (delta T between room and glycol = true), the control will operate the 
second cooling source control and compressor control simultaneously if needed.
If the Minimum CW Temp is disabled, the second cooling source temperature is ignored, the control 
will always operate the second cooling source and compressors simultaneously when the load requires 
it.
75
71
72
73
74
70
Increasing Temperature
Cool 2
On
Cool 1
On
+ 100 % 
Cooling
Valve 100% 
Open
Valve 
Closed
½ Dead-
band
76
77
78
79
+ 200% 
Cooling
0%
Cooling
2nd
Source
Comp
½ Proportional Band
½ Proportional Band
Band1: 2
nd
 Source
Band 2: Compressors
Temp Setpoint: 70°F
Proportional Band: 8°F
Deadband: 2°F