Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 84
Operation
24
Figure 19 Three-stage heating
0%
Heating
65
70
Heat 3
On
½ Dead-
band
66
67
68
69
Heat 2
On
Heat 1
On
Heat 3
Off
Heat 2
Off
Heat 1
Off
-100 %
Heating
½ Proportional Band
Decreasing Temperature
Temp Setpoint: 70°F
Proportional Band: 8°F
Deadband: 2°F