User Menu Parameters
51
7.0
U
SER
 M
ENU
 P
ARAMETERS
User menus report general cooling unit operations and status. The password for the user menu is 
1490.
The iCOM control firmware is being updated constantly. As a result, the User menu parameter tables 
in this manual may be slightly different than what is shown on your cooling unit's display. Please 
 for the latest iCOM User manual updates.
Spare Part List—Large Display Only
Displays the various Liebert part numbers for all parts in the cooling unit to simplify ordering 
replacement parts.
Table 12
Setpoints parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 1
Password
PASSWORD
W
-
Temperature Setpoint
TEMP SET
W
41-104°F (5-40°C)
Humidity Setpoint
HUM SET
W
20-80%
(settings lower than 19%
will be forced to 20)
Humidity Control Type
HUM CTRL
W
Relative, Compensated,
Predictive
Supply Limit
SUP LIM
W
Enabled, Disabled
Supply Limit Temp Value
SUP TEMP
W
41-77°F (5-25°C)
Backup Temperature 
Setpoint
BACK TPS
W
41-104°F (5-40°C)
Table 13
Spare part list parameters—large display only
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 1
List of parts
N/A
R
-
Table 14
Event log parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 1
Last 400 events
Last 400 events
R
-
Table 15
View network parameters—large display only*
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 1
Status Unit 1—32
N/A
R
AlarmOff, Manual, LocalOff, SystemOff,
AlarmStandby, Standby, TimerOff,
SystemOn, WarningOn, AlarmOn, Timer
* Permits viewing all units connected in a network. Viewable on a large display only.
°C / °F
% RH
SET
EVENT 
LOG