User Menu Parameters
52
Table 16
 Set alarms parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 1
Password
PASSWORD
W
-
Return Sensor Alarms
RTN SNSR
W
Enabled, Disabled
High Return Temperature
HI TEMP
W
34-210°F (1-99°C)
Low Return Temperature
LO TEMP
W
34-210°F (1-99°C)
High Return Humidity
HI HUM
W
1-99%
Low Return Humidity
LOW HUM
W
1-99%
Sensor A Alarms
SENSOR A
W
Enabled, Disabled
High Temperature Sensor A
HI TEMP A
W
34-210°F (1-99°C)
Low Temperature Sensor A
LO TEMP A
W
34-210°F (1-99°C)
High Humidity Sensor A
HI HUM A
W
1-99%
Low Humidity Sensor A
LO HUM A
W
1-99%
Table 17
Sensor data
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 2
Optional Sensor A Temperature
TEMP A
R
32-122°F (0-50°C)
Optional Sensor A Humidity
HUM A
R
20-80%
Optional Sensor B Temperature
TEMP B
R
32-122°F (0-50°C)
Optional Sensor B Humidity
HUM B
R
20-80%
Optional Sensor C Temperature
TEMP C
R
32-122°F (0-50°C)
Optional Sensor C Humidity
HUM C
R
20-80%
Freecooling Fluid Temperature
FC TEMP
R
4-113°F (-15 to 45°C)
Outdoor Temperature
AMB TEMP
R
4-113°F (-15 to 45°C)
Freecooling Status
FC STATE
R
Off, Start, On, Blank
DigiScroll 1 Temperature
DS1 TEMP
R
84-313°F (29-156°C)
DigiScroll 2 Temperature
DS2 TEMP
R
84-313°F (29-156 °C)
Page 2 of 2
Daily High Temperature
Hi Temp
R
32-122°F (0-50°C)
Daily High Temperature
Hi Te H
Hi Te M
Hi Te S
R
-
Daily Low Temperature
Lo Temp
R
32-122°F (0-50°C)
Daily Low Temperature
Lo Te H
Lo Te M
Lo Te S
R
-
Daily High Humidity
Hi Humi
R
20-80%
Daily High Humidity
Hi Hu H
Hi Hu M
Hi Hu S
R
-
SET
ALARMS