Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 84
Service Menu Parameters
61
Table 27
Diagnostics / service mode parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 7
Password
PASSWORD
W
-
HP 1 Alarm Code
HP1  CODE
W
0-999
HP 2 Alarm Code
HP2 CODE
W
0-999
HT 1 Alarm Counter
HT1 CNT
W
0-999
HT 2 Alarm Counter
HT2 CNT
W
0-999
LP 1 Alarm Code
LP 1 CODE
W
0-999
LP 2 Alarm Code
LP2 CODE
W
0-999
Actual LP1 Pressure
LP1 ACT
R
- 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Actual LP2 Pressure
LP2 ACT
R
- 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Actual HP1 Pressure
HP1 ACT
R
- 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Actual HP2 Pressure
HP2 ACT
R
- 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Page 2 of 7
Password
PASSWORD
W
-
Manual Mode
MANUAL
W
No, Yes
Motor(s)
MOTOR(S)
W
Off, On
Compressor 1
COMP1
W
Off, On
Compressor 1
C1 MODE
W
Run, Evacuate, Charge
Compressor 1 Capacity
C1 CAP
W
Off, On
Compressor 1 Cycle Ramp
C1 CYCLE
W
0-100%
Compressor 1 LLSV
LLSV 1
W
Off, On
Compressor 2
COMP2
W
Off, On
Compressor 2
C2 MODE
W
Run, Evacuate, Charge
Compressor 2 Capacity
C2 CAP
W
Off, On
Compressor 2 Cycle Ramp
C2 CYCLE
W
0-100%
Compressor 2 LLSV
LLSV 2
W
Off, On
Page 3 of 7
Password
PASSWORD
W
-
Electric Heat 1 (or HG/HW)
EL HEAT1
W
Off, On
Electric Heat 2 (or E.Heat 1)
EL HEAT2
W
Off, On
Electric Heat 3 (or E.Heat 2)
EL HEAT3
W
Off, On
SCR Heat
SCR HEAT
W
0-100%
Dehumidification Output
DEHUM
W
Off, On
Humidfier Fill
HUM FILL
W
Off, On
Humidifier
HUM
W
Off, On
Humidfier Drain
H DRAIN
W
Off, On
Humidifier Current
HUM.C.
R
0.00 - 99.99A
Page 4 of 7
SERVICE