Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 84
Service Menu Parameters
63
Page 7of 7
Status Humidifier Problem
HUM PROB
R
OK, Act
Status DT1 (Outdoor/Glycol)
DT1
R
OK, Act
Status DT2 (Glycol/Room)
DT2
R
OK, Act
Status DT3 (Room/Setpoint)
DT3
R
OK, Act
Status Min CW
MIN CW
R
OK, Act
LWD Value
LWD Val
R
Off, On
Status LSI
LSI
R
Off, On
Table 28
Set alarms parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 7
Password
PASSWORD
W
-
Return Sensor Alarms
RTN SNSR
W
Disabled, Enabled
High Return Temperature
HI TEMP
W
34-210°F (1-99°C)
Low Return Temperature
LO TEMP
W
34-210°F (1-99°C)
High Return Humidity
HI HUM
W
1-99%
Low Return Humidity
LOW HUM
W
1-99%
Sensor A Alarms
SENSOR A
W
Disabled, Enabled
High Temperature Sensor A
HI TEMPA
W
34-210°F (1-99°C)
Low Temperature Sensor A
LO TEMPA
W
34-210°F (1-99°C)
High Humidity Sensor A
HI HUM A
W
1-99%
Low Humidity Sensor A
LO HUM A
W
1-99%
Table 27
Diagnostics / service mode parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
SERVICE
SET
ALARMS