        Cyclades PM IPDU Installer/Administrator/User Guide
Syntax 
current [<IPDU#>|<IPDU_ID>]|reset
Arguments
<IPDU#>
 
IPDU number in a daisy chain
<IPDU_ID> 
Identification string previously set by the id command
reset
 
Clears the saved peak current value
Examples
To get the current status for all units, enter the following.
To get the current status for a specific unit, enter the following.
To reset maximum current drawn, enter the following:
currentprotection
The currentprotection command turns on and off the over current protection feature. The 
overcurrent protection does not let any outlet be turned on if the current drawn by the unit is greater 
than the current threshold configured with the command alarm. This command may also be used to 
display the current protection status. This command is available to the admin user only.
Syntax 
currentprotection <on|off|status>
Arguments
on
 
Enables over current protection
off
 
Disables over current protection
status
 
Displays the current protection status
 
pm> current
IPDU #1: True RMS current: 2.2A. Maximum current: 9.4A
IPDU #2: True RMS current: 2.0A. Maximum current: 10.2A 
pm> current 2
IPDU #2: True RMS current: 2.4A. Maximum current: 10.2A
pm>current reset
IPDU #1: Clearing maximum recorded current to zero.
IPDU #2: Clearing maximum recorded current to zero.