Crestron electronic TPS-GA-TPI Manual De Usuario

Descargar
Página de 56
Crestron TPS-GA-TPI  
Isys
®
 G-Series Touchpanel Interface
 
Operations Guide – DOC. 6501 
Isys
®
 G-Series Touchpanel Interface: TPS-GA-TPI  
  43 
Program Checks 
Actions that can be performed on the TPS-GA-TPI vary depending on whether it is 
connected via Cresnet or Ethernet. 
Cresnet Connections 
  For Cresnet connections, display the network device tree (Tools | Network Device 
Tree) to show all network devices connected to the control system. Right-click on 
the TPS-GA-TPI to display actions that can be performed on the TPS-GA-TPI. 
Ethernet Connections 
  For Ethernet connections, display the “System Info window (click the 
 icon) and 
select the Functions menu to display actions that can be performed on the  
TPS-GA-TPI. 
Be sure to use the Crestron Toolbox to create the TPS-GA-TPI IP table. 
•  Select Functions | IP Table Setup. 
•  Add, modify or delete entries in the IP table. The TPS-GA-TPI can have 
only one IP table entry. 
•  A defined IP table can be saved to a file or sent to the device. 
Edit the control system’s IP table to include an entry for the TPS-GA-TPI. The entry 
should list the TPS-GA-TPI’s IP ID (specified on the TPS-GA-TPI’s IP table) and 
the internal gateway IP address 127.0.0.1.