DeviceNet Network Scanner DVPDNET-SL
 
DVP-PLC Application Manual 
3. Power, MS, NS LED 
8. Function switch 
4. DIN rail clip 
9. DeviceNet connection port 
5. Digital indicator 
 
2.3 DeviceNet 
Connection 
Port 
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with 
DVPDNET-SL. 
PIN 
Signal 
Color 
Content 
1 V- Black 
VDC 
2 CAN_L  Blue  Signal- 
3 SHIELD 
Shielded 
4 CAN_H White Signal+ 
5 V+  Red 
24 
VDC 
 
1
2
3
4
5
 
2.4 Address 
Switch 
The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99 
are forbidden). 
Switch setting 
Content 
0 … 63 
Valid DeviceNet node address 
64…99 
Invalid DeviceNet node address 
9
1
6
4
5
0
0
9
1
3
2
7
8
2
5
6
4
3
7
8
 
Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding 
switch of x10
1
 to 2 and the corresponding switch of x10
0
 to 6. 
Note: 
z  Please set up the node address when the power is switched off. After the setup is completed, re-power 
DVPDNET-SL. 
z  When DVPDNET-SL is operating, changing the setting of node address will be invalid. 
z  Use slotted screwdriver to rotate the switch carefully in case you scratch the switch. 
2.5 Function 
Switch 
The function switches are for: 
„  Setting up the work mode (IN0) 
„  Setting up the baud rate of DeviceNet (DR0 ~ DR1)
 
DR1 
DR0 
Baud rate 
OFF OFF 
125 
kbps 
OFF ON 
250 
kbps 
ON OFF 
500 
kbps 
ON ON 
Incorrect 
setting 
IN0 
ON 
When the slave is off-line, the I/O data in 
the buffer area will be held.