DeviceNet Network Scanner DVPDNET-SL
 
DVP-PLC Application Manual 
7
OFF 
When the slave is off-line, the I/O data in 
the buffer area will be cleared.   
IN1 Reserved 
Note: 
z  Please set up the function switch when the power is switched off. After the setup is completed, re-power 
DVPDNET-SL. 
z  When DVPDNET-SL is operating, changing the setting of the function switch will be invalid. 
z  Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch. 
2.6 Digital 
Indicator 
The digital indicator provides the following two functions: 
DVPDNET
POWER
MS
NS
 
1.  Displaying the node address and error messages of DVPDNET-SL and error messages. 
2.  Displaying the error message of slave. 
2.7 Extension 
Port 
The extension port is used on connecting DVPDNET-SL to the left-side extension port on DVP-SV PLC MPU 
or to other extension modules connected to the left side of DVP-SV. 
3 Basic 
Operation 
3.1 
Connecting DVPDNET-SL to DVP-SV MPU 
„  Adjust the extension clip on the left side of DVP-SV. 
„  Meet the extension port of the MPU with DVPDNET-SL as shown in the figure below. 
„  Fasten the extension clip. 
DVPDNET
DVP28SV
RUN
STOP
 
3.2 
Installing DVPDNET-SL and DVP-SV MPU on DIN Rail 
„  Use 35mm DIN rail.