Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide
73
53-1002373-02
Installing a Brocade MLXe-4 router
2
FIGURE 47
installing the router in a rack
4. Slide the router down so that the mounting screw heads are in the narrowest part of the 
keyhole slots.
5. Tighten the screws to secure the router in place. For extra support, use additional screws.
NOTE
For better grounding of the router to the rack, attach the router using star washers. You should also 
use star washers with any single-hole grounding lugs to keep the lugs from rotating.
6. Repeat step 2 through step 5 to mount each router in the rack, moving from lowest to highest.
Installing Brocade MLXe-4 modules
The sequence for installing multiple modules is important to ensure proper fit. The recommended 
sequence for the Brocade MLXe-4 router is to install right-to-left, beginning with the lowest row and 
moving up.
For instructions about installing 2x100GbE interface modules, refer to 
NOTE
Installation procedures are identical for interface, management and switch fabric modules. 
DANGER
The intra-building ports of the equipment or subassembly is suitable for connection to 
intra-building or unexposed wiring or cabling only. The intra-building ports of the equipment or 
subassembly MUST NOT be metallically connected to interfaces that connect to the outside plant 
(OSP) or its wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 
or Type 4 ports as described in GR-1089-CORE, Issue 5) and require isolation from the exposed 
OSP cabling. The addition of Primary Protectors is not sufficient protection in order to connect 
these interfaces metallically to OSP wiring.
1
Screws on mounting posts
2
Front-mount position
3 Mid-mount position
1
1
2
3